Plan Review Notes
Plan Review Notes For Permit 20040893
Permit Number 20040893
Review Stop B
Sequence Number 2
Notes
Date Text
2020-06-22 10:20:57SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK
 SHALL COMPLY WITH THE MATERIALS AND METHODS
 REQUIREMENTS IN THE FLORIDA BUILDING CODE.
  
 ORIGINAL COMMENT:
 1- PROVIDE COMPLETE SET OF DRAWINGS PREPARED (SIGNED &
 SEALED)BY REGISTERED DESIGN PROFESSIONAL AS REQUIRED BY
 CHAPTER 471, FLORIDA STATUTES & 61G15 FLORIDA
 ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES &
 61G1 FLORIDA ADMINISTRATIVE CODE SHOWING ALL THE
 PROPOSED SCOPE OF WORK. SEC. 107.1 CITY AMENDMENTS.
  
 RESPONSE:
 (A) PROPOSED STOREFRONT PLAN ON SHEET A1 SHOWS THAT
 EXISTING EGRESS DOORS ON THE ROOM ADJACENT TO THE
 "EXISTING GATHERING HALL WERE REDUCED. DEMO PLAN ON THE
 SAME SHEET SHOWS DOUBLE DOORS, WHILE PROPOSED PLAN
 SHOWS ONLY ONE DOOR. PLEASE IDENTIFY THE USE OF THIS
 ROOM AND SHOW THAT THE PROPOSED SINGLE DOOR IS ADEQUATE
 TO COMPLY WITH THE EGRESS REQUIREMENTS OF THIS ROOM.
 SEC. 702.6 FBC-EXISTING BUILDING. SEC. 1004.1
 FBC-BUILDING.
  
 (B) PROVIDE COMPLETE SIGNED AND SEALED STRUCTURAL
 FRAMING DETAILS AND SPECIFICATIONS FOR THE STEEL
 FRAMING TO RECEIVE THE PROPOSED 144"X92 ALUMINUM
 SLIDING GLASS DOORS. SPECIFY ALL FRAMING MEMBERS AND
 CONNECTORS. SEC. 702.6 FBC-EXISTING BUILDING. SEC.
 1609.1 FBC-BUILDING.
  
  
 2- OK
 3- OK
 4- OK
  
 5- NOTE: ADDITIONAL INFORMATION ADDED TO HELP EXPEDITE
 THE REVIEW AND PERMITTING PROCESS.
 PROPOSED SLIDING GLASS DOORS NEED TO COMPLY WITH SEC.
 1010.1.4.3 FBC-BUILDING. AND ELECTRICAL PERMIT WILL BE
 REQUIRED.
 SEE COPY OF SEC. 1010.1.4.3 FBC-BUILDING BELOW:
  
 1010.1.4.3 SPECIAL PURPOSE HORIZONTAL SLIDING,
 ACCORDION OR FOLDING DOORS.
 IN OTHER THAN GROUP H OCCUPANCIES, SPECIAL PURPOSE
 HORIZONTAL SLIDING, ACCORDION OR FOLDING DOOR
 ASSEMBLIES PERMITTED TO BE A COMPONENT OF A MEANS OF
 EGRESS IN ACCORDANCE WITH EXCEPTION 6 TO SECTION
 1010.1.2 SHALL COMPLY WITH ALL OF THE FOLLOWING
 CRITERIA:
  
 1.THE DOORS SHALL BE POWER OPERATED AND SHALL BE
 CAPABLE OF BEING OPERATED MANUALLY IN THE EVENT OF
 POWER FAILURE.
  
 2.THE DOORS SHALL BE OPENABLE BY A SIMPLE METHOD FROM
 BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR EFFORT.
  
 3.THE FORCE REQUIRED TO OPERATE THE DOOR SHALL NOT
 EXCEED 30 POUNDS (133 N) TO SET THE DOOR IN MOTION AND
 15 POUNDS (67 N) TO CLOSE THE DOOR OR OPEN IT TO THE
 MINIMUM REQUIRED WIDTH.
  
 4.THE DOOR SHALL BE OPENABLE WITH A FORCE NOT TO EXCEED
 15 POUNDS (67 N) WHEN A FORCE OF 250 POUNDS (1100 N) IS
 APPLIED PERPENDICULAR TO THE DOOR ADJACENT TO THE
 OPERATING DEVICE.
  
 5.THE DOOR ASSEMBLY SHALL COMPLY WITH THE APPLICABLE
 FIRE PROTECTION RATING AND, WHERE RATED, SHALL BE
 SELF-CLOSING OR AUTOMATIC CLOSING BY SMOKE DETECTION IN
 ACCORDANCE WITH SECTION 716.5.9.3, SHALL BE INSTALLED
 IN ACCORDANCE WITH NFPA 80 AND SHALL COMPLY WITH
 SECTION 716.
  
 6.THE DOOR ASSEMBLY SHALL HAVE AN INTEGRATED STANDBY
 POWER SUPPLY.
  
 7.THE DOOR ASSEMBLY POWER SUPPLY SHALL BE ELECTRICALLY
 SUPERVISED.
  
 8.THE DOOR SHALL OPEN TO THE MINIMUM REQUIRED WIDTH
 WITHIN 10 SECONDS AFTER ACTIVATION OF THE OPERATING
 DEVICE.
  
  
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved