| 2020-05-05 14:11:59 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20040884 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PLEASE SUBMIT A MECHANICAL DRAWING SHOWING THE |
| | REQUIRED HEATING OF THIS NEW SPACE. PLEASE SHOW HOW YOU |
| | ARE GOING TO CONDITION THIS NEW BEDROOM. IF YOU ARE |
| | GOING TO USE EXISTING MECHANICAL SYSTEM, PLEASE SHOW |
| | THE EXISTING SYSTEM IS SIZED TO ACCOMMODATE THE |
| | ADDITIONAL LOAD. PROVIDE ENERGY SUBMITTAL AND MANUAL J. |
| | FBC FS 107.2, FBC EC 101.5.1.1.2 |
| | |
| | 2) THIS WILL REQUIRE A MECHANICAL SUB-PERMIT. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |