| 2020-09-17 13:36:13 | 3RD REVIEW FBC-2017 PLUMBING |
| | PERMIT 20040876 |
| | 9/17/2020 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | COMMENTS 5F, 5J, & 8 LISTED BELOW FROM THE 1ST AND 2ND |
| | REVIEWS LISTED BELOW HAVE NOT BEEN ADDRESSED- PLEASE |
| | COMPLY WITH THE COMMENTS. |
| | |
| | 5) SHEET A.09- |
| | F) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF |
| | GRAB BARS- SECTION 604.5 REFER TO FIGURES 604.5.1 AND |
| | 604.5.2 FOR CORRECT POSITIONING AND LENGTHS OF THE GRAB |
| | BARS. REFER TO SECTION 609.4 CORRECT MOUNTING HEIGHTS |
| | OF THE BARS- 33 INCHES MINIMUM AND 36 INCHES MAXIMUM |
| | ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF THE |
| | GRIPPING SURFACE. (SEE FIGURE 604.5.2: THE REAR GRAB |
| | SHALL BE LOCATED TO PROVIDE A MINIMUM 12 IN. EXTENSION |
| | FROM THE CENTER OF THE WATER CLOSET TO THE ADJACENT |
| | WALL. THE DRAWING SHOWS AN EXTENSION OF 16-18 IN. FROM |
| | THE CENTER TO THE WALL AND A 6 IN. SPACE BETWEEN THE |
| | BAR AND THE WALL, THEREFORE THE 18 IN. EXTENSION WOULD |
| | BE COMPLIANT, BUT A 16 IN. EXTENSION WOULD NOT BECAUSE |
| | THE BAR WOULD ONLY EXTEND 10IN. FROM THE CENTER OF THE |
| | WATER CLOSET- PLEASE CORRECT THE DETAIL.) |
| | J) MIRROR: THE MIRROR SHALL BE INSTALLED WITH THE |
| | BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES MAXIMUM |
| | ABOVE THE FINISH FLOOR OR GROUND- SECTION 603.3. |
| | |
| | 8) FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | WATER HEATERS- SECTION 502.1 FBC P. THE SPECS WERE NOT |
| | SUBMITTED HOWEVER A REVIEW OF THE SPECS ON THE EEEMAX |
| | WEBSITE INDICATE THE SELECTED EX2412 IS LIMITED TO 0.5 |
| | GPM FLOW RATE AT 33 DEGREE F TEMPERATURE RISE. THE |
| | TANKLESS HEATERS ARE ADEQUATE FOR THE REQUIRED 0.4 GPM |
| | FLOW RATE AT THE LAVATORIES, HOWEVER THEY ARE |
| | UNDERSIZED FOR THE MOP SINK AND THE KITCHEN SINK WHICH |
| | REQUIRE FLOW RATES OF 3 AND 1.75 GPM FLOW RATES. |
| | |
| | 9) SHEET A-01: PLEASE OUTLINE THE SLAB DEMOLITION AREA |
| | FOR NEW DRAIN INSTALLATIONS, AND PROVIDE A SLAB REPAIR |
| | DETAIL- SECTION 107.2.1 WPB AND SECTION 1816 FBC B. |
| | |
| | 10) SUBMIT A PLUMBING SUB-PERMIT APPLICATION PER |
| | SECTION 105.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |