| 2020-08-05 17:02:12 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT 20040876 |
| | 8/5/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | COMMENTS FROM THE 1ST REVIEW LISTED BELOW WILL BE |
| | MARKED AS PASSED OR FAILED. ADDITIONAL NOTES IN CAPITOL |
| | LETTERS WILL BE ADDED TO FAILED COMMENTS. |
| | |
| | 1) PASSED. SHEET P.01: SHOW A FULL-OPEN TYPE VALVE WILL |
| | BE INSTALLED ON THE DISCHARGE SIDE OF THE WATER METER- |
| | SECTION 606.1(3) FBC P. |
| | |
| | 2) PASSED. P-01 & P.02: MODIFY THE DRAWINGS TO INCLUDE |
| | ANY PLUMBING FIXTURES IN THE KITCHEN- ICE MAKER, |
| | DISHWASHER ETC- SECTION 107.2.1 WPB. |
| | |
| | 3) PASSED. P-02: SHOW THE REQUIRED WATER HAMMER |
| | ARRESTORS FOR THE WATER LINE TO THE EWC- 604.9 FBC P. |
| | PLEASE NOTE THAT WATER HAMMER ARRESTORS ARE ALSO |
| | REQUIRED ON THE REFRIGERATOR ICE MAKER LINE AND |
| | DISHWASHER SUPPLY LINE IF THOSE ITEMS ARE BEING |
| | INSTALLED. - SECTION 604.9 FBC P. |
| | |
| | 4) PASSED. SHEET A.09: THE TOILET ROOMS SHALL BE |
| | IDENTIFIED AS EITHER MALE OR FEMALE PER SECTION 403.2 |
| | FBC P. |
| | |
| | 5) A.09: PLEASE PROVIDE ENLARGED DIMENSIONED DRAWINGS |
| | OF THE MEN'S AND WOMEN'S TOILET ROOMS TO SHOW |
| | COMPLIANCE WITH SECTION 213.2 FBC ACC. THE ENLARGED |
| | DRAWINGS AND ELEVATION VIEWS SHALL SHOW: |
| | A) PASSED. CLEAR FLOOR SPACES FOR THE WATER CLOSETS- |
| | SECTION 604.3 FBC ACC. |
| | B) PASSED. CLEAR FLOOR SPACES FOR THE LAVATORIES- |
| | SECTION 606.2. |
| | C) PASSED. TURNING SPACES IN THE TOILET ROOMS- SECTION |
| | 304.3. |
| | D) PASSED. CENTERLINES OF THE WATER CLOSETS FROM THE |
| | SIDE WALLS OR PARTITIONS- SECTION 604.2. |
| | E) FAILED. HEIGHTS OF THE WATER CLOSET SEATS FROM THE |
| | FINISHED FLOORS- SECTION 604.4. THE DETAIL SHOWS THE |
| | HEIGHT DIMENSION TO THE RIM AND NOT THE SEAT. |
| | F) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF |
| | GRAB BARS- SECTION 604.5 REFER TO FIGURES 604.5.1 AND |
| | 604.5.2 FOR CORRECT POSITIONING AND LENGTHS OF THE GRAB |
| | BARS. REFER TO SECTION 609.4 CORRECT MOUNTING HEIGHTS |
| | OF THE BARS- 33 INCHES MINIMUM AND 36 INCHES MAXIMUM |
| | ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF THE |
| | GRIPPING SURFACE. |
| | G) PASSED. LOCATIONS OF FLUSH CONTROLS- SECTION 604.6. |
| | H) FAILED LOCATIONS, CLEARANCES, AND MOUNTING HEIGHTS |
| | FOR DISPENSERS- SECTION 604.7. MOUNTING HEIGHT NOT |
| | SHOWN. |
| | I) THE KNEE AND TOE CLEARANCES FOR THE LAVATORY ARE NOT |
| | SHOWN- SEE SECTIONS 306 AND FIGURES 306.2 AND 306.3. |
| | J) MIRROR: THE MIRROR SHALL BE INSTALLED WITH THE |
| | BOTTOM EDGE OF THE REFLECTING SURFACE 40 INCHES MAXIMUM |
| | ABOVE THE FINISH FLOOR OR GROUND- SECTION 603.3. |
| | |
| | 6) FAILED. PROVIDE ACCESSIBILITY COMPLIANCE DETAILS FOR |
| | THE NEW DRINKING FOUNTAIN- CLEAR FLOOR SPACE APPROACH, |
| | KNEE AND TOE CLEARANCES, SPOUT HEIGHTS ETC- SECTION |
| | 602.1 FBC ACC. NOT PROVIDED ON THE PLANS. |
| | |
| | 7) PASSED. PROVIDE ACCESSIBILITY COMPLIANCE DETAILS FOR |
| | THE KITCHENETTE SINK- CLEAR FLOOR SPACE APPROACHES |
| | WAITING SINK RIM OR COUNTER HEIGHT, AND KNEE AND TOE |
| | CLEARANCES- SECTION 606.1 FBC ACC. |
| | |
| | 8) PASSED. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | WATER HEATERS- SECTION 502.1 FBC P. |
| | |
| | 9) TEMPERED WATER IS REQUIRED FOR THE NEW LAVATORIES |
| | PER SECTION 416.5 FBC P. PLEASE MODIFY THE ISOMETRIC |
| | AND FLAT LINE DRAWINGS TO SHOW THE LOCATIONS OF THE |
| | MIXING VALVE SHOWN ON SHEET P-00. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |