| Plan Review Notes For Permit 20040876 |
| Permit Number |
20040876 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-08-05 11:31:10 | PLAN DENIED | | | 1) PROVIDE DUCT SIZE ON ALL DUCT NEW AND EXISTING | | | SECTION 107 FBC 2017 | | | 2) DUCT DETECTORS SHALL BE INSTALLED ON THE SUPPLY SIDE | | | OF THE AIR CONDITIONING | | | EQUIPMENT. SECTION 606.2.1 FBC (M) 2017 | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|