Plan Review Notes For Permit 20040876
Permit Number 20040876
Review Stop M
Sequence Number 2
Notes
Date Text
2020-08-05 11:31:10PLAN DENIED
 1) PROVIDE DUCT SIZE ON ALL DUCT NEW AND EXISTING
 SECTION 107 FBC 2017
 2) DUCT DETECTORS SHALL BE INSTALLED ON THE SUPPLY SIDE
 OF THE AIR CONDITIONING
 EQUIPMENT. SECTION 606.2.1 FBC (M) 2017
  