2020-08-11 09:01:17ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PREVIOUS COMMENTS THAT HAVE BEEN SATSFIED WILL BE
 MARKED AS SUCH.
  
 1) RISER SUPPLIED BUT IT SHOWS A 400A MAIN FEEDING A
 GUTTER AND A TAP GOING TO A 600A MDP THEN TO PANEL "B"
  
 2) LOAD CALCULATION FOR PANEL "B" IS COMPLETE BUT YOU
 NEED TO SUPPLY ONE FOR THE 400A MAIN AND THE 600 MDP
  
 3) FAULT CURRENT CALCULATION IS DONE BUT STATES
 EXISTING ON PANE L"B".
  
 4) LIGHTING CONTROL NOT SHOWN FBC 405.2
  
 5) COMPLETE.