| Plan Review Notes For Permit 20040876 |
| Permit Number |
20040876 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-08-11 09:01:17 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | PREVIOUS COMMENTS THAT HAVE BEEN SATSFIED WILL BE | | | MARKED AS SUCH. | | | | | | 1) RISER SUPPLIED BUT IT SHOWS A 400A MAIN FEEDING A | | | GUTTER AND A TAP GOING TO A 600A MDP THEN TO PANEL "B" | | | | | | 2) LOAD CALCULATION FOR PANEL "B" IS COMPLETE BUT YOU | | | NEED TO SUPPLY ONE FOR THE 400A MAIN AND THE 600 MDP | | | | | | 3) FAULT CURRENT CALCULATION IS DONE BUT STATES | | | EXISTING ON PANE L"B". | | | | | | 4) LIGHTING CONTROL NOT SHOWN FBC 405.2 | | | | | | 5) COMPLETE. |
|