Plan Review Notes
Plan Review Notes For Permit 20040876
Permit Number 20040876
Review Stop P
Sequence Number 1
Notes
Date Text
2020-05-15 15:14:12 
 1ST REVIEW FBC-2017 PLUMBING
 PERMIT 20040876
 5/15/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P.01: SHOW A FULL-OPEN TYPE VALVE WILL BE
 INSTALLED ON THE DISCHARGE SIDE OF THE WATER METER-
 SECTION 606.1(3) FBC P.
  
 2) P-01 & P.02: MODIFY THE DRAWINGS TO INCLUDE ANY
 PLUMBING FIXTURES IN THE KITCHEN- ICE MAKER, DISHWASHER
 ETC- SECTION 107.2.1 WPB.
  
 3) P-02: SHOW THE REQUIRED WATER HAMMER ARRESTORS FOR
 THE WATER LINE TO THE EWC- 604.9 FBC P. PLEASE NOTE
 THAT WATER HAMMER ARRESTORS ARE ALSO REQUIRED ON THE
 REFRIGERATOR ICE MAKER LINE AND DISHWASHER SUPPLY LINE
 IF THOSE ITEMS ARE BEING INSTALLED. - SECTION 604.9 FBC
 P.
  
 4) SHEET A.09: THE TOILET ROOMS SHALL BE IDENTIFIED AS
 EITHER MALE OR FEMALE PER SECTION 403.2 FBC P.
  
 5) A.09: PLEASE PROVIDE ENLARGED DIMENSIONED DRAWINGS
 OF THE MEN'S AND WOMEN'S TOILET ROOMS TO SHOW
 COMPLIANCE WITH SECTION 213.2 FBC ACC. THE ENLARGED
 DRAWINGS AND ELEVATION VIEWS SHALL SHOW:
 A) CLEAR FLOOR SPACES FOR THE WATER CLOSETS- SECTION
 604.3 FBC ACC.
 B) CLEAR FLOOR SPACES FOR THE LAVATORIES- SECTION
 606.2.
 C) TURNING SPACES IN THE TOILET ROOMS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALLS
 OR PARTITIONS- SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS- SECTION 604.5
 G) LOCATIONS OF FLUSH CONTROLS- SECTION 604.6.
 H) LOCATIONS, CLEARANCES, AND MOUNTING HEIGHTS FOR
 DISPENSERS- SECTION 604.7.
  
 6) PROVIDE ACCESSIBILITY COMPLIANCE DETAILS FOR THE NEW
 DRINKING FOUNTAIN- CLEAR FLOOR SPACE APPROACH, KNEE AND
 TOE CLEARANCES, SPOUT HEIGHTS ETC- SECTION 602.1 FBC
 ACC.
  
 7) PROVIDE ACCESSIBILITY COMPLIANCE DETAILS FOR THE
 KITCHENETTE SINK- CLEAR FLOOR SPACE APPROACHES WAITING
 SINK RIM OR COUNTER HEIGHT, AND KNEE AND TOE
 CLEARANCES- SECTION 606.1 FBC ACC.
  
 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER
 HEATERS- SECTION 502.1 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  