| 2020-05-15 15:14:12 | |
| | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT 20040876 |
| | 5/15/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P.01: SHOW A FULL-OPEN TYPE VALVE WILL BE |
| | INSTALLED ON THE DISCHARGE SIDE OF THE WATER METER- |
| | SECTION 606.1(3) FBC P. |
| | |
| | 2) P-01 & P.02: MODIFY THE DRAWINGS TO INCLUDE ANY |
| | PLUMBING FIXTURES IN THE KITCHEN- ICE MAKER, DISHWASHER |
| | ETC- SECTION 107.2.1 WPB. |
| | |
| | 3) P-02: SHOW THE REQUIRED WATER HAMMER ARRESTORS FOR |
| | THE WATER LINE TO THE EWC- 604.9 FBC P. PLEASE NOTE |
| | THAT WATER HAMMER ARRESTORS ARE ALSO REQUIRED ON THE |
| | REFRIGERATOR ICE MAKER LINE AND DISHWASHER SUPPLY LINE |
| | IF THOSE ITEMS ARE BEING INSTALLED. - SECTION 604.9 FBC |
| | P. |
| | |
| | 4) SHEET A.09: THE TOILET ROOMS SHALL BE IDENTIFIED AS |
| | EITHER MALE OR FEMALE PER SECTION 403.2 FBC P. |
| | |
| | 5) A.09: PLEASE PROVIDE ENLARGED DIMENSIONED DRAWINGS |
| | OF THE MEN'S AND WOMEN'S TOILET ROOMS TO SHOW |
| | COMPLIANCE WITH SECTION 213.2 FBC ACC. THE ENLARGED |
| | DRAWINGS AND ELEVATION VIEWS SHALL SHOW: |
| | A) CLEAR FLOOR SPACES FOR THE WATER CLOSETS- SECTION |
| | 604.3 FBC ACC. |
| | B) CLEAR FLOOR SPACES FOR THE LAVATORIES- SECTION |
| | 606.2. |
| | C) TURNING SPACES IN THE TOILET ROOMS- SECTION 304.3. |
| | D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE WALLS |
| | OR PARTITIONS- SECTION 604.2. |
| | E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED |
| | FLOORS- SECTION 604.4. |
| | F) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| | BARS- SECTION 604.5 |
| | G) LOCATIONS OF FLUSH CONTROLS- SECTION 604.6. |
| | H) LOCATIONS, CLEARANCES, AND MOUNTING HEIGHTS FOR |
| | DISPENSERS- SECTION 604.7. |
| | |
| | 6) PROVIDE ACCESSIBILITY COMPLIANCE DETAILS FOR THE NEW |
| | DRINKING FOUNTAIN- CLEAR FLOOR SPACE APPROACH, KNEE AND |
| | TOE CLEARANCES, SPOUT HEIGHTS ETC- SECTION 602.1 FBC |
| | ACC. |
| | |
| | 7) PROVIDE ACCESSIBILITY COMPLIANCE DETAILS FOR THE |
| | KITCHENETTE SINK- CLEAR FLOOR SPACE APPROACHES WAITING |
| | SINK RIM OR COUNTER HEIGHT, AND KNEE AND TOE |
| | CLEARANCES- SECTION 606.1 FBC ACC. |
| | |
| | 8) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WATER |
| | HEATERS- SECTION 502.1 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |