| Date |
Text |
| 2020-04-30 15:53:08 | 1). A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE |
| | COMPLETED AT THIS TIME DUE TO LACK OF INFORMATION |
| | SUBMITTED ON THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS |
| | MAY BE GENERATED DURING PLAN RESUBMISSION. |
| | 2). SHEET A 11 - THERE IS NO INDICATION OF A MIXED OR |
| | SEPARATED OCCUPANCY; MERCANTILE IS INDICATED. |
| | 3). INDICATE IF THE UNIT IS DESIGNED FOR MIXED USE |
| | (NON-SEPARATED) OR SEPARATED USE PER SECTION 6.1.14.1 |
| | OF NFPA 101 FLORIDA EDITION 2015. FOR NON-SEPARATED |
| | MIXED USE OCCUPANCIES, THE MOST STRINGENT FIRE AND LIFE |
| | SAFETY REQUIREMENTS OF EACH OCCUPANCY SHALL APPLY TO |
| | THE BUILDING. |
| | 4). PER NFPA 101 CH 6, OCCUPANCY CLASSIFICATION |
| | |
| | 6.1 CLASSIFICATION OF OCCUPANCY. |
| | 6.1.1 GENERAL. |
| | 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A |
| | BUILDING OR |
| | STRUCTURE, OR PORTION OF A BUILDING OR STRUCTURE, SHALL |
| | BE CLASSIFIED IN |
| | ACCORDANCE WITH 6.1.2 THROUGH 6.1.13. OCCUPANCY |
| | CLASSIFICATION SHALL BE |
| | SUBJECT TO THE RULING OF THE AUTHORITY HAVING |
| | JURISDICTION WHERE THERE IS A |
| | QUESTION OF PROPER CLASSIFICATION IN ANY INDIVIDUAL |
| | CASE. |
| | |
| | 6.1.14.2 DEFINITIONS. |
| | 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE |
| | IN WHICH TWO |
| | OR MORE CLASSES OF OCCUPANCY EXIST. |
| | 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE |
| | THE |
| | OCCUPANCIES ARE INTERMINGLED. |
| | 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY |
| | WHERE THE |
| | OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCE RATED |
| | ASSEMBLIES. |
| | 6.1.14.3 MIXED OCCUPANCIES. |
| | 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE |
| | CLASSIFIED AS TO ITS USE IN |
| | ACCORDANCE WITH SECTION 6.1. |
| | 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST |
| | RESTRICTIVE |
| | REQUIREMENTS OF THE OCCUPANCIES INVOLVED, UNLESS |
| | SEPARATE SAFEGUARDS |
| | ARE APPROVED. |
| | 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.) |
| | 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED, |
| | EACH PART OF THE |
| | BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED |
| | IN THIS CHAPTER, |
| | SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY |
| | FIRE-RESISTIVE |
| | ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3, |
| | TABLE 6.1.14.4.1(A), |
| | AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED |
| | BY APPROVED |
| | EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY |
| | 6.1.14.4.6. |
| | |
| | 5).PER FBC SECTION 508.2 AGGREGATE ACCESSORY |
| | OCCUPANCIES SHALL NOT OCCUPY MORE THAN TEN PERCENT IN |
| | WHICH THEY ARE LOCATED. |
| | 6).PER SECTION 8.7, ANY AREA (STORAGE) HAVING A DEGREE |
| | OF HAZARD GREATER THAN NORMAL TO THE GENERAL OCCUPANCY |
| | (MERCANTILE) OF THE BUILDING, SHALL BE SEPARATED FROM |
| | NON-STORAGE AREAS WITH A 1-HOUR FIRE-RATED BARRIER OR |
| | BE PROTECTED WITH AN AUTOMATIC SPRINKLER SYSTEM. DOORS |
| | SHALL BE SELF CLOSING, POSITIVE LATCHING, AND |
| | FIRE-RATED FOR AT LEAST 45-MINUTES. |
| | 7).NO DIMENSIONS GIVEN FOR CORRIDOR WIDTH. |
| | |
| | 8).PER NFPA , CH 7 MEANS OF EGRESS |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM |
| | THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY |
| | TO DOOR |
| | LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO |
| | ELEVATED |
| | TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON |
| | LABORATORY |
| | FIRE TEST PROCEDURES. |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A |
| | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM |
| | THE EGRESS |
| | SIDE. |
| | 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3 |
| | SHALL NOT |
| | APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH |
| | 23. |
| | |
| | 9). WHAT MEASURES WILL BE IMPLEMENTED TO ENSURE THAT |
| | THE ROLLUP DOOR WILL NOT BE CLOSED WHEN THE BUILDING IS |
| | OCCUPIED. |
| | 10). MANUFACTURER SPECIFICATION SHEETS TO BE PROVIDED |
| | FOR ALL EQUIPMENT TO BE INSTALLED FOR EGRESS DOORS. |
| | 11).WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | 12).NEW RESTROOM INSTALLATION APPEARS TO BLOCK THE |
| | MEANS OF EGRESS WITH AN OUTWARD SWINGING DOOR. |
| | |
| | S. THOMAS |
| | 561-804-4728 |