Plan Review Notes
Plan Review Notes For Permit 20040876
Permit Number 20040876
Review Stop E
Sequence Number 1
Notes
Date Text
2020-05-12 15:53:24ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) RISER DIAGRAM SHOWIING SERVICE DISCONNETS AND
 PANELS, 215.5
 PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE
 EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND
 BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR PANEL.
 SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING
 TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94,
 408.30
  
 2) LOAD CALCULATION FOR THE TENNANT SPACE 220.2
 PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING
 AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS
 ADEQUATE. NEC 215.2, 220, 408.30
  
 3) AIC RATING OF SERVICE DISCONNECT AND PANELS 110.
 PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
  
 4) NO LIGHTING CONTROL SHOWN OR LIGHTING DENSITIES
 PROVIDE A NOTE TO INDICATE COMPLIANCE WITH FBC CE 405.2
 AUTOMATIC LIGHTING CONTROL AND LIGHTING DENSITIES PER
 CODE SECTION.
  
 5) NEED TO LABEL AREAS IN BUILDING BACK AREA IS BEING
 USED FOR ?????