| 2020-05-12 15:53:24 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) RISER DIAGRAM SHOWIING SERVICE DISCONNETS AND | | | PANELS, 215.5 | | | PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF SERVICE | | | EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, WIRE AND | | | BREAKER SIZES FOR SERVICE AND FEED TO INTERIOR PANEL. | | | SHOW GEC SIZE AND SYSTEM, SHOW INTERSYSTEM BONDING | | | TERMINATION POINT. NEC 215.5, 230, 250.50, 250.94, | | | 408.30 | | | | | | 2) LOAD CALCULATION FOR THE TENNANT SPACE 220.2 | | | PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING | | | AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE IS | | | ADEQUATE. NEC 215.2, 220, 408.30 | | | | | | 3) AIC RATING OF SERVICE DISCONNECT AND PANELS 110. | | | PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | | NEC 110.9, 110.10 | | | | | | 4) NO LIGHTING CONTROL SHOWN OR LIGHTING DENSITIES | | | PROVIDE A NOTE TO INDICATE COMPLIANCE WITH FBC CE 405.2 | | | AUTOMATIC LIGHTING CONTROL AND LIGHTING DENSITIES PER | | | CODE SECTION. | | | | | | 5) NEED TO LABEL AREAS IN BUILDING BACK AREA IS BEING | | | USED FOR ????? |
|