| 2020-05-06 09:39:40 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THE IS NO INDICATION OF THE ADDRESS ON THE PLAN |
| | SHEET. |
| | |
| | PLEASE PROVIDE |
| | |
| | |
| | |
| | 2) THERE IS NO INDICATION OF THE OCCUPANCY TYPE PER THE |
| | FLORIDA FIRE PREVENTION CODE AND WHAT THE BUSINESS DOES |
| | ON THE PLAN SHEET. |
| | |
| | PER NFPA 101, CH. 6 |
| | |
| | 6.1 CLASSIFICATION OF OCCUPANCY. |
| | 6.1.1 GENERAL. |
| | 6.1.1.1 OCCUPANCY CLASSIFICATION. THE OCCUPANCY OF A |
| | BUILDING OR |
| | STRUCTURE, OR PORTION OF A BUILDING OR STRUCTURE, SHALL |
| | BE CLASSIFIED IN |
| | ACCORDANCE WITH 6.1.2 THROUGH 6.1.13. OCCUPANCY |
| | CLASSIFICATION SHALL BE |
| | SUBJECT TO THE RULING OF THE AUTHORITY HAVING |
| | JURISDICTION WHERE THERE IS A |
| | QUESTION OF PROPER CLASSIFICATION IN ANY INDIVIDUAL |
| | CASE. |
| | |
| | PLEASE PROVIDE |
| | |
| | |
| | |
| | 3) THERE ARE INDICATION ON THE PLAN SHEET OF NEW DOORS; |
| | HOWEVER, THERE IS NO DOOR SCHEDULE NOR DOOR HARDWARE. |
| | |
| | HARDWARE ON DOORS IN THE MEANS OF EGRESS SHALL COMPLY |
| | WITH NFPA 101, CH 7 |
| | |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM |
| | THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. |
| | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY |
| | TO DOOR |
| | LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER EXPOSURE TO |
| | ELEVATED |
| | TEMPERATURE IN ACCORDANCE WITH THE LISTING, BASED ON |
| | LABORATORY |
| | FIRE TEST PROCEDURES. |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A |
| | TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM |
| | THE EGRESS |
| | SIDE. |
| | 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3 |
| | SHALL NOT |
| | APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 THROUGH |
| | 23. |
| | 7.2.1.5.5 KEY-OPERATED LOCKS. |
| | 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE |
| | PERMITTED TO HAVE |
| | KEY-OPERATED LOCKS FROM THE EGRESS SIDE, PROVIDED THAT |
| | ALL OF THE |
| | FOLLOWING CRITERIA ARE MET: |
| | (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11 |
| | THROUGH 43 FOR |
| | THE SPECIFIC OCCUPANCY. |
| | (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS |
| | THAN 1 IN. |
| | (25 MM) HIGH ON A CONTRASTING BACKGROUND THAT READS AS |
| | FOLLOWS IS LOCATED ON OR ADJACENT TO THE DOOR LEAF: |
| | THIS |
| | DOOR TO REMAIN UNLOCKED WHEN THE |
| | BUILDING IS OCCUPIED. |
| | (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY |
| | DISTINGUISHABLE |
| | AS LOCKED. |
| | (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT |
| | INSIDE THE |
| | BUILDING WHEN IT IS LOCKED. |
| | |
| | PLEASE PROVIDE AND ENSURE COMPLAINCE |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |