Plan Review Notes
Plan Review Notes For Permit 20040872
Permit Number 20040872
Review Stop E
Sequence Number 1
Notes
Date Text
2020-05-20 11:11:39ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NEED TO SHOW LAYOUT OF FIXTURES THAT ARE BEING
 REPLACED.
  
 2) SUBMIT CUTSHEETS OF NEW FIXTURES
  
 110.3 ( B) INSTALLATION AND USE. LISTED OR LABELED
 EQUIPMENT SHALL BE INSTALLED AND USED IN ACCORDANCE
 WITH ANY INSTRUCTIONS INCLUDED IN THE LISTING OR
 LABELING.
  
 3) SHOW COMPLIANCE WITH THE ENERGY CODE FOR LIGHTIING
 CONTROL.
  
 PROVIDE LIGHTING CONTROL PER FBC ENERGY CODE. FBC CE
 405.2.2.2
  
 4) PLAN NOT SIGNED.
  
 PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE DESIGN
 PROFESSIONAL RESPONSIBLE FOR THE DESIGN. FBC 107.2.1,
 FS 471, 481