| Plan Review Notes For Permit 20040872 |
| Permit Number |
20040872 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-05-20 11:11:39 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) NEED TO SHOW LAYOUT OF FIXTURES THAT ARE BEING | | | REPLACED. | | | | | | 2) SUBMIT CUTSHEETS OF NEW FIXTURES | | | | | | 110.3 ( B) INSTALLATION AND USE. LISTED OR LABELED | | | EQUIPMENT SHALL BE INSTALLED AND USED IN ACCORDANCE | | | WITH ANY INSTRUCTIONS INCLUDED IN THE LISTING OR | | | LABELING. | | | | | | 3) SHOW COMPLIANCE WITH THE ENERGY CODE FOR LIGHTIING | | | CONTROL. | | | | | | PROVIDE LIGHTING CONTROL PER FBC ENERGY CODE. FBC CE | | | 405.2.2.2 | | | | | | 4) PLAN NOT SIGNED. | | | | | | PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE DESIGN | | | PROFESSIONAL RESPONSIBLE FOR THE DESIGN. FBC 107.2.1, | | | FS 471, 481 |
|