| 2021-12-16 14:42:03 | 1ST REVIEW FBC-2020 PLUMBING |
| | PERMIT- 20040867 |
| | 12/16/21 |
| | |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | WPB CROSS CONNECTION CONTROL MANUAL- WPB CCCM |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P1: 3RD REQUEST FOR CIVIL DRAWINGS AND |
| | BACKFLOW PREVENTER SPECIFICATIONS. COPIED BELOW ARE THE |
| | 1ST AND 2ND PLUMBING REVIEW COMMENTS REQUESTING THE |
| | DRAWINGS AND BACKFLOW PREVENTER LOCATION AND SPECS. THE |
| | ENGINEER'S RESPONSE NARRATIVE INDICATE THE PDF'S WERE |
| | SUBMITTED HOWEVER IT APPEARS THEY WERE NOT UPLOADED FOR |
| | REVIEW. THE PLANS SETS SHALL INCLUDE WATER/SEWER AND |
| | DRAINAGE PLANS. WATER/SEWER SHALL SHOW LOCATIONS OF |
| | WATER MAIN, POINT OF WATER SERVICE CONNECTION, METER |
| | AND BACKFLOW LOCATION, SEWER LATERAL, SEWER/BUILDING |
| | DRAIN POINT OF CONNECTION. DRAINAGE PLANS SHALL SHOW |
| | STORM DRAIN LATERAL AND BUILDING STORM DRAIN POINTS OF |
| | CONNECTION, AND/OR LOCATIONS OF ROOF DRAINAGE AREAS, |
| | AND CATCH BASINS- SECS. 107.2.1, 110.9 WPB AND SEC. |
| | 1101.2 FBC P. |
| | |
| | PREVIOUS PLUMBING COMMENTS: |
| | D. SEE PLAN SHEET P.1: PER WPB FBC 107.2.1, WPB CCCM |
| | AND FBC PL 608, PROVIDE SPECIFICATION, DETAIL AND |
| | LOCATION FOR THE WATER SERVICE BACKFLOW PREVENTER. |
| | RESPONSE: CIVIL DRAWINGS TO ADDRESS. |
| | NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE CIVIL |
| | DRAWINGS; PROVIDE SPECIFICATION, DETAIL AND LOCATION |
| | FOR THE WATER SERVICE BACKFLOW PREVENTER COMPLYING WITH |
| | WPB CCCM AND FBC PL 608. |
| | E. SECOND REQUEST; SEE PLAN SHEET P.1: PER WPB FBC |
| | 107.2.1, PROVIDE CIVIL DRAWINGS NOTED AT SERVICE |
| | CONNECTIONS. |
| | PLEASE NOTE: A PLUMBING PERMIT WILL NOT BE ISSUED WITH |
| | OUT THE CIVIL DRAWINGS SHOWING THE REQUESTED |
| | INFORMATION FOR THE BACKFLOW PREVENTER. WPB FBC |
| | 107.2.1.2. |
| | |
| | NEW COMMENT: A SEPARATE PERMIT IS REQUIRED FOR |
| | ISTALLATION OF THE POTABLE WATER SERVICE BACKFLOW |
| | PRVENTER. |
| | PLEASE NOTE THAT A FL. LICENSED PLUMBING CONTRACTOR |
| | SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE |
| | BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB |
| | AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL |
| | BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |