| Date |
Text |
| 2021-12-01 09:14:14 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| | SERVICES/ BUILDING DIVISION |
| | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20040867 |
| | ADD: 936 27TH ST. |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: ??? |
| | E-MAIL: [email protected] CONTACT: MATTHEW DONNELL |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2ND REVIEW |
| | DATE: TUES. AUGUST 03RD/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. VALUATION. |
| | |
| | 2) COMPLIED. |
| | |
| | |
| | 3A-B) COMPLIED. |
| | |
| | 3C)PROVISO/ NOTICE NO ACTION REQUIRED. THERE IS A |
| | DETAIL FOR THE DUMPSTER ENCLOSURE, PLEASE NOTE THE |
| | DUMPSTER ENCLOSURE TAKES A SEPARATE, REVIEW AND |
| | ASSOCIATED FEES. |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATIVE CODE 105.1. |
| | |
| | 3D) PROVISO/ NOTICE NO ACTION REQUIRED. JUST TO THE |
| | RIGHT OF THE FLOOR PLAN SHOWS A CONCRETE SLAB WITH (3) |
| | 500 GALLON FUEL TANKS. FUEL TANKS ALSO TAKE SEPARATE |
| | PERMITS REVIEWS AND ASSOCIATED FEES. 2017 FLORIDA |
| | BUILDING CODE W 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FLORIDA BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE |
| | 105.1. |
| | |
| | 3E) NOT APPLICABLE. |
| | |
| | 4) SHEET 003 4.1 COMPLIED PRESSURES IN VASD. THANK YOU. |
| | |
| | |
| | 5) BUILDING PROVISO: WELDED OR BOLTED CONNECTIONS, THE |
| | CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| | SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| | QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| | STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON |
| | THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL |
| | BE REQUIRED. |
| | 2017 FBC-B 2204.1 WELDING |
| | 1. WELD PROCEDURES SPECIFICATIONS |
| | 2. QUALIFICATIONS OF WELDING PERSONAL |
| | 2017 FBC-B 2204.2 BOLTING. |
| | IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED, |
| | PLEASE CONTACT THE CHIEF BUILDING INSPECTOR KEN CONRAD |
| | AT |
| | 561-805-6666. |
| | |
| | 6A) 2ND REQUEST. FOR METAL BUILDINGS THE WALL AND ROOF |
| | PRODUCT APPROVALS ARE REQUIRED BEFORE PERMIT ISSUANCE |
| | JUST AS THE BUILDING SHOP DRAWINGS ARE REQUIRED, TO |
| | VERIFY GIRT & PURLIN SPACING AND PRESSURES MATCH FOR |
| | THE WALL END ZONE 5 AND ROOF CORNER ZONE 3. MOST OF THE |
| | TIME THE GIRTS AND PURLINS NEED TO BE SPACED CLOSER |
| | TOGETHER FOR THE HIGHER PRESSURES IN THESE ZONES. |
| | COMPONENTS & CLADDING PLEASE SUPPLY THE PRODUCT |
| | APPROVAL FULL REPORTS. IF IN THE PRODUCT APPROVAL THERE |
| | ARE MULTIPLE SUB-SYSTEMS APPROVED IDENTIFY (CIRCLE) |
| | WHICH APPLICATION IS TO BE INSTALLED. |
| | 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| | OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| | RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| | OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| | APPROVALS: |
| | (31)(A) EXTERIOR DOORS |
| | (B) WINDOWS & MULLIONS |
| | (C) PANEL WALLS: METAL WALL PANELS, LOUVERS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES, METAL ROOF PANELS, |
| | |
| | 6B) 3RD REQUEST. RESPONSE COMMENT INDICATES WALL AND |
| | ROOF PANEL PRODUCT APPROVALS ATTACHED. NO PRODUCT |
| | APPROVALS ARE ATTACHED. |
| | W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE |
| | 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 6C) DELEGATED ENGINEERING. 61G15-30.003 ENGINEERING |
| | DOCUMENT CLASSIFICATION. FL 61G-15-30.006 (3) THE |
| | DELEGATED ENGINEER SHALL FORWARD THE DELEGATED |
| | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR |
| | REVIEW. |
| | |
| | 7) THE SHEETS SUBMITTED BY MBMI 4/ 10 ROOF FRAMING |
| | PURLIN SPACING @ 3FEET 5 ? INCH SPACING & GIRTS AND |
| | SHEET 5/10 END WALL AND SIDE WALL FRAMING WITH VARIED |
| | SPACING, BUT IN THE END WALL ZONES SAME SPACING AS WALL |
| | ZONE 4. NEED PRODUCT APPROVALS TO VERIFY SPACING AND |
| | THE ASSOCIATED PRESSURES. |
| | THE MISSING INFORMATION IS THE PRODUCT APPROVAL FOR THE |
| | METAL EXTERIOR WALL SYSTEM AND METAL ROOF SYSTEM. |
| | WITHOUT THE PRODUCT APPROVALS BEING SUBMITTED, |
| | IDENTIFYING THE TYPE OF WALL AND ROOF PANELS BEING |
| | INSTALLED, WITH THEIR ALLOWABLE SPACING BETWEEN |
| | SUPPORTS AND ASSOCIATED PRESSURES NO REVIEW FOR THE |
| | STRUCTURAL PORTION OF THE BUILDING CAN BE COMPLETED. |
| | |
| | 8) SEMI COMPLIED. IS THE ENGINEER FOR MBMI TAKING THE |
| | DOUBLE REDUCTION IN ROOF PANEL PRESSURES, IT IS NOT |
| | STATED, AND WITHOUT THE ROOFING PRODUCT APPROVAL |
| | VERIFICATION OF ROOF DESIGN PANEL AND TYPE OF PANEL |
| | LOCKING DEVICE CANNOT BE VERIFIED. |
| | THE OTHER UNKNOWN IS IF THE ENGINEER OF RECORD FOR MBMI |
| | HAS DESIGNED THE ROOF SYSTEM TO SECTION 2211.5 OF THE |
| | FBC-B AISI S210 OR AISI S 100? WITH A GREATER DEDUCTION |
| | IN PRESSURES THAN ALLOWED IN VASD? |
| | |
| | 9) NEW COMMENT. MBMI SHEET 6 END WALL FRAMING LINE 3 |
| | EC-2 SIDE SHOWS 6 GIRTS WHEREAS SIDE EC-5 ONLY SHOWS 5. |
| | END WALL FRAMING LEFT SIDE ON THE LEFT SIDE IT IS |
| | DIMENSIONED AS A GIRT BEING THERE BUT NOT SHOWN AGAIN |
| | THE RIGHT SIDE DOES NOT SHOW BUT 5 GIRTS. 107.2.1.2 |
| | ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 10) NEW COMMENT. SITE PLAN SP-1 CHANGE SHOWS THE |
| | PROPOSED BUILDING 5 FEET FROM THE PROPERTY LINE. WITH |
| | THE BUILDING TYPE BEING DECLARED TYPE IIB/ S1 |
| | OCCUPANCY, AND 5 FEET FROM THE PROPERTY LINE THIS WALL |
| | WILL NEED TO BE 1 HOUR FIRE RATED PER TABLE 602 OF THE |
| | 2020 FBC-BUILDING CODE. |
| | |
| | 11) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN ( NO |
| | PRODUCT APPROVALS) SINCE THERE WAS A GREAT DEFICIENCY |
| | IN PLANS AND REQUIRED DOCUMENTATION. WITH THE NEXT PLAN |
| | REVIEW CYCLE THERE MAYBE ADDITIONAL REVIEW COMMENTS |
| | BECAUSE OF NEW PLANS AND INFORMATION LACKING UNDER THE |
| | PRIOR REVIEW. |
| | |
| | MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE |
| | WORKING FROM CITY HALL. |
| | MY WORK HOURS ARE TUES. & WED. 7:30 AM- 4:30 PM |
| | PART-TIME/ RETIRED. |
| | |
| | IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET |
| | BACK INTO THE OFFICE CALL |
| | (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL. |
| | THANK YOU. |
| | |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |