| 2021-08-05 16:27:54 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20040867 936 27TH ST |
| | |
| | 2ND REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | |
| | A.NEW COMMENTS REGARDING ICE MACHINE IN SCOPE OF WORK: |
| | 1.PER WPB FBC 107.2.1, SHOW COLD WATER ROUTING TO ICE |
| | MACHINE ON FLOOR PLAN TO MATCH RISER DIAGRAM. |
| | 2.PER FBC PL 606.2.2 AND 606.3, PROVIDE DEDICATED, |
| | ACCESSIBLE SHUT OFF VALVE FOR HOSE BIB AT ICE MACHINE |
| | VICINITY |
| | 3.PER FBC PL 606.2.3 AND 606.3, PROVIDE DEDICATED, |
| | ACCESSIBLE SHUT OFF VALVE FOR ICE MACHINE. |
| | |
| | |
| | B.NEW COMMENT REGARDING RECIRCULATING PUMP PIPING |
| | DETAIL: |
| | PER FBC 107.2.1, |
| | 1.SHOW COLD WATER TO WATER HEATER; SHOW SHUT OFF VALVE |
| | AT UPSTREAM END, FOLLOWED BY CHECK VALVE, THEN |
| | EXPANSION TANK THEN RETURN CONNECTION, THEN CONNECTION |
| | TO WATER HEATER. |
| | 2.SHOW RETURN WITH BALL VALVE AT UPSTREAM END, FOLLOWED |
| | BY CHECK VALVE THEN THE PUMP AND CONNECTION TO COLD |
| | WATER |
| | |
| | C. SEE PLAN SHEET P.1: PER WPB FBC 107.2.1, PROVIDE A |
| | NOTE STATING ?ALL PIPING SHALL BE SUPPORTED IN |
| | ACCORDANCE WITH 2017 FBC PLUMBING CODE SECTION 308?. |
| | COMPLIED |
| | NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE HANGER DETAIL |
| | WITH HANGER TYPE, ROD AND ATTACHMENTS TO STRUCTURE. |
| | |
| | D. SEE PLAN SHEET P.1: PER WPB FBC 107.2.1, WPB CCCM |
| | AND FBC PL 608, PROVIDE SPECIFICATION, DETAIL AND |
| | LOCATION FOR THE WATER SERVICE BACKFLOW PREVENTER. |
| | RESPONSE: CIVIL DRAWINGS TO ADDRESS. |
| | NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE CIVIL |
| | DRAWINGS; PROVIDE SPECIFICATION, DETAIL AND LOCATION |
| | FOR THE WATER SERVICE BACKFLOW PREVENTER COMPLYING WITH |
| | WPB CCCM AND FBC PL 608. |
| | |
| | E. SECOND REQUEST; SEE PLAN SHEET P.1: PER WPB FBC |
| | 107.2.1, PROVIDE CIVIL DRAWINGS NOTED AT SERVICE |
| | CONNECTIONS. |
| | PLEASE NOTE: A PLUMBING PERMIT WILL NOT BE ISSUED WITH |
| | OUT THE CIVIL DRAWINGS SHOWING THE REQUESTED |
| | INFORMATION FOR THE BACKFLOW PREVENTER. WPB FBC |
| | 107.2.1.2. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| | DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | MOBILE 561-246-0882 |
| | PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND |
| | THURSDAYS |
| | |
| | 20040867 936 27TH ST |