| 2020-07-30 17:36:13 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20040867 936 27TH ST |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | 1. A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS |
| | REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW |
| | PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL |
| | PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST |
| | BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW |
| | APPROVAL. |
| | 2. A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS |
| | HAS BEEN MADE BASED UPON INFORMATION PROVIDED ON PLAN |
| | SHEET 1.1; CODE SUMMARY. |
| | 3. SEE PLAN SHEET 3.1: PER WPB FBC 107.2.1, SHOW |
| | TURNING SPACE FOR WATER CLOSET COMPLYING WITH FBC ACC |
| | 304.3.1 OR 304.3.2. |
| | 4. 5. SEE PLAN SHEET 3.1: THE FLOOR PLAN DETAIL THE |
| | DOOR SWINGS INTO THE CLEAR FLOOR SPACE OF THE LAVATORY |
| | AND WATER CLOSET; PLEASE SHOW COMPLIANCE WITH FBC ACC |
| | 603.2.3 AND OR EXCEPTIONS ON THE DETAIL FLOOR PLAN |
| | 6. SEE PLAN SHEET 3.1: JUST TO THE RIGHT OF THE FLOOR |
| | PLAN SHOWS A CONCRETE SLAB WITH AN ICE MACHINE AND (3) |
| | 500 GALLON FUEL TANKS. IS THE CONCRETE SLAB AND |
| | EQUIPMENT IN THE SCOPE OF WORK? PER WPB FBC 107.2.1, |
| | CLARIFY. PLEASE NOTE THAT WATER SUPPLY TO THE ICE |
| | MACHINE IS REQUIRED AND RISER AND PLAN VIEW OF PIPING |
| | WITH REQUIRED BACKFLOW PROTECTION IS REQUIRED PER FBC |
| | PL CHAPTER 6. FUEL TANKS ALSO TAKE SEPARATE PERMITS |
| | REVIEWS AND ASSOCIATED FEES. 2017 FLORIDA BUILDING CODE |
| | W/2017 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATIVE CODE 105.1. |
| | 7. SEE PLAN SHEET P.1: THE PLUMBING LEGEND TEXT IS NOT |
| | LEGIBLE. PER WPB FBC 107.2.1, CORRECT DEFICIENCY. |
| | 8. SEE PLAN SHEET P.1: PER FBC PL 608.1, MOP SERVICE |
| | SINK FAUCET SHALL BE PROVIDED WITH A BACKFLOW |
| | PREVENTIVE DEVICE. |
| | 9. SEE PLAN SHEET P.1: PER WPB FBC 107.2.1, PROVIDE |
| | MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL FOR |
| | THE ELECTRIC WATER HEATER. |
| | 10. SEE PLAN SHEET P.1: PER WPB FBC 107.2.1, PROVIDE |
| | MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL FOR |
| | THE WATER HEATER SUPPORT BRACKET AND ON THE PLAN |
| | PROVIDE A DETAIL FOR SAME TO INCLUDE ANCHORING. |
| | 12. 11. SEE PLAN SHEET P.1: WATER RISER; PER WPB FBC |
| | 107.2.1, SHOW WATER SUPPLY TO P-1 WATER CLOSET. |
| | 13. SEE PLAN SHEET P.1: COMPRESSED AIR; PER WPB FBC |
| | 107.2.1,PROVIDE A RISER DIAGRAM. |
| | 14. SEE PLAN SHEET P.1: PER WPB FBC 107.2.1, PROVIDE A |
| | NOTE STATING "ALL PIPING SHALL BE SUPPORTED IN |
| | ACCORDANCE WITH 2017 FBC PLUMBING CODE SECTION 308". |
| | 15. SEE PLAN SHEET P.1: PER WPB FBC 107.2.1, WPB CCCM |
| | AND FBC PL 608, PROVIDE SPECIFICATION, DETAIL AND |
| | LOCATION FOR THE WATER SERVICE BACKFLOW PREVENTER. |
| | 16. SEE PLAN SHEET P.1: PER WPB FBC 107.2.1, PROVIDE |
| | CIVIL DRAWINGS NOTED AT SERVICE CONNECTIONS. |
| | |
| | A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT |
| | THIS TIME. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS AND A |
| | RESPONSE NARRATIVE ADDRESSING THE PLUMBING COMMENTS |
| | FROM THE FIRST REVIEW. |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| | DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |
| | |
| | 20040867 936 27TH ST |
| | |
| | |