Plan Review Notes
Plan Review Notes For Permit 20040762
Permit Number 20040762
Review Stop B
Sequence Number 1
Notes
Date Text
2020-04-28 11:59:252017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 20040762
 ADD: 3515 S DIXIE HWY.
 CONT: BEST INDUSTRIES
 TEL: 772-460-8130
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. APRIL 28TH/2020
 ACTION: DENIED
  
 1) THE DOCUMENT SUBMITTED FROM MDM SERVICES BY ENG.
 RICHARD R. MORRIS, A-1.03 & 8X11 SHEET WOULD APPEAR TO
 HAVE BEEN DIGITALLY SIGNED THEN DOWNLOADED AND THEN
 RE-UPLOADED. THIS DOCUMENT CANNOT BE OPENED TO VERIFY
 AUTHORIZATION. 61G15-23.005 PROCEDURES FOR SIGNING AND
 SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 FLORIDA ADMINISTRATIVE CODE 61G15-23.005 (3)(C) A
 SCANNED, FACSIMILE, DIGITALLY CREATED OR COPIED IMAGE
 OF THE LICENSEE?S SIGNATURE SHALL NOT BE USED ON
 ELECTRONICALLY SIGNED AND SEALED ENGINEERING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 2) SHEET A1-03 WIND DESIGN LIST THE PRESSURES AS IN
 ZONE 1 -36.7, ZONE 2 -43.4 AND ZONE 3 AS -43.4. WE
 CALCULATE THE PRESSURES FOR 10 SQ. FT./ MEAN ROOF 15
 FEET, EXP. C AS ZONE 1, -37.9, ZONE 2 -63.9 AND ZONE 3
 -95.7. PLEASE NOTE IN VIEWING THIS PROPERTY ON P. B. C.
 MY GEO NAV THERE IS ONLY A PARAPET ON 3 SIDES OF THE
 ROOF NONE SHOWN ON THE BACK OF THE STRUCTURE.
 ROOFS NO ZONE 3/ PARAPET. ASCE 7-10 FIGURE 30.4-2A.
 FOOTNOTE 5. IF A PARAPET IS EQUAL TO OR HIGHER THAN 3
 FEET IS PROVIDED AROUND THE PERIMETER OF THE ROOF WITH
 0<7 DEGREES THE NEGATIVE VALUE OF GCP IN ZONE 3 SHALL
 BE EQUAL TO THOSE IN ZONE 2 AND THE POSITIVE VALUES OF
 GCP IN ZONES 2 AND 3 SHALL BE EQUAL TO THOSE IN WALL
 ZONES 4 AND 5 RESPECTIVELY, SEE FIGURE 30.4-1.
  
 3) WELDED OR BOLTED CONNECTIONS. THE CONTRACTOR IS
 REQUIRED TO PROVIDE WELD PROCEDURE SPECIFICATIONS &
 WELDER OPERATOR PERFORMANCE QUALIFICATION RECORDS IN
 ACCORDANCE WITH THE REFERENCED STANDARDS AT TIME OF
 INSPECTION.
 2017 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2) QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF THERE ARE ANY QUESTIONS ABOUT THESE REQUIREMENTS
 PLEASE CONTACT KEN CONRAD CHIEF BUILDING INSPECTOR AT
 561-805-6666.
  
 4) NOTE ONLY. ROOF COVERING UNDER SEPARATE PERMIT.
  
 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved