| 2020-05-11 09:14:30 | DESIGNER SENT EXISTING DRAWINGS FOR THE MECHANICAL |
| | SYSTEM IN THIS AREA. I CAN NOW SEE HOW THE SYSTEM WAS |
| | DESIGNED. NO ADDITIONAL DUCTWORK NEEDED. |
| 2020-04-23 10:10:00 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20040759 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) IT APPEARS THAT THIS PROJECT IS TAKING AN OPEN |
| | CORRIDOR AND INSTALLING DOORS TO CREATE A SUITE. PLEASE |
| | PROVIDE A COMPLETE SET OF MECHANICAL DRAWINGS SHOWING |
| | EXISTING CONDITIONS, DEMO CONDITIONS AND PLANNED REWORK |
| | OF THE MECHANICAL SYSTEM IN THIS AREA. SHOW HOW THE |
| | SYSTEM WILL BE PROVIDING AIR TO THE NEW SUITE. FBC FS |
| | 107.2.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |
| | MICHAEL EDWARDS |
| | MECHANICAL EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL. 33401 |
| | 561-805-6728 |
| | [email protected] |
| | |