| 2020-04-28 11:01:24 | JERRY SMITH |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | |
| | |
| | 1ST REVIEW |
| | GAS COMMENTS: DENIED |
| | PER WPB FBC 107.2.1, CLEARLY PROVIDE CALCULATIONS FOR |
| | COMBUSTION AIR FOR RANGE (PROVIDE FBC FG CODE SECTION, |
| | I.E. 304.5.) AND DRYER COMPLYING WITH FBC FG 304.1 AND |
| | 614.6. IT APPEARS THAT THE PLAN SHEET A-1 FLOOR PLAN |
| | FROM MASTER PERMIT 19081209 SUBMITTED INDICATES A DRYER |
| | VENT, NOT A DUCT FOR PROVIDING COMBUSTION AIR TO THE |
| | UNIT. PLEASE NOTE THAT A SEPARATE MECHANICAL PERMIT AND |
| | PLAN/DETAIL IS REQUIRED FOR THE COMBUSTION AIR DUCT |
| | INDICATED ON THE ISOMETRIC DRAWING FOR THE DRYER |
| | COMBUSTION AIR. THE COMBUSTION AIR CALCULATIONS FOR ALL |
| | AFFECTED UNITS SHOULD BE INCLUDED IN THIS SUBMITTAL AS |
| | WELL. |
| | |
| | PROVISO |
| | PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE AS A |
| | DEFERRED SUBMITTAL MANUFACTURER?S SPECIFICATION AND |
| | INSTALLATION GUIDES FOR THE MP REGULATORS AND GAS |
| | APPLIANCES. DOCUMENT SHALL BE SUBMITTED, APPROVED AND |
| | ON SITE PRIOR TO FINAL INSPECTION. PROCEED AT YOUR OWN |
| | RISK. |
| | |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS |
| | REQUIRED BY FAC AND FS. |
| | ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| | DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |
| | |
| | 20040758 208 SUMMA ST |
| | MASTER PERMIT 19081209 |
| | |
| | PHONE 561-805-6715 |
| | PLUMBING COMMENTS: APPROVED |
| | ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD |
| | INSPECTOR'S APPROVAL |
| | |
| | |
| | PLUMBING COMMENTS: APPROVED WITH PROVISO |
| | |
| | |
| | PLUMBING COMMENTS: DENIED |
| | |
| | |
| | AS THE PLANS ARE NOT SIGNED AND SEALED BY A |
| | PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN |
| | SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE |
| | DESIGNER PER WPB FBC 107.2.1. |
| | |
| | |