| 2020-04-29 13:31:55 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT-20040725 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M0.2- IN THE KITCHEN HOOD MAKE-UP AIR UNIT |
| | SCHEDULE REMARKS, BOTH KSF-1 AND KSF-3 CALL FOR A NOTE |
| | 12. THERE IS NO NOTE 12 IN THE REMARKS. PLEASE SHOW |
| | NOTE 12 IN THE REMARKS SECTION. FBC FS 107.2.1 |
| | |
| | 2) SHEET M1.2- VENTILATION NOTE; VENTILATION SHOULD BE |
| | BASED ON ASHRAE 62.1 ? 2013, NOT 2010 VERSION. FBC M |
| | 403.3.1.1.2.3.2 |
| | |
| | 3) SHEET M1.2- PLEASE SHOW AN AIR BALANCE REPORT FOR |
| | THIS FACILITY. I DO NOT SEE THE HOOD EXHAUST RATES IN |
| | YOUR CHARTS. FBC M 508.1.2 |
| | |
| | 4) SHEET M1.2- TG-1 IN THE BATHROOM AREA IS USING THE |
| | RETURN SYMBOL, PLEASE CORRECT THIS AS YOU CANNOT USE |
| | THE BATHROOMS AS RETURN AIR. FBC M TABLE 403.3.1.1 |
| | (NOTE G) |
| | |
| | 5) SHEET M3.2- PLEASE SHOW A DETAIL DRAWING OF HOW |
| | KSF-2 IS COMPLYING WITH THE MAKEUP AIR TEMPERATURE |
| | REQUIREMENT. FBC M 508.1.1 |
| | |
| | 6) CAPTIVE AIRE HOODS SHEETS ARE NOT INCLUDED IN THIS |
| | PROJECT PACKAGE. SEPARATE PLAN REVIEWS AND PERMITS WILL |
| | BE REQUIRED FOR THE HOOD SYSTEMS ON THIS PROJECT. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |