Plan Review Notes
Plan Review Notes For Permit 20040685
Permit Number 20040685
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2020-04-17 12:44:56THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 THE PROPOSED PROJECT SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 101 CH 40 INDUSTRIAL OCCUPANCIES40.1 GENERAL
 REQUIREMENTS.
  
 40.1.1 APPLICATION.
 40.1.1.1 THE REQUIREMENTS OF THIS CHAPTER SHALL APPLY
 TO BOTH NEW
 AND EXISTING INDUSTRIAL OCCUPANCIES.
 40.1.1.2 ADMINISTRATION. THE PROVISIONS OF CHAPTER 1,
 ADMINISTRATION, SHALL APPLY.
 40.1.1.3 GENERAL. THE PROVISIONS OF CHAPTER 4, GENERAL,
 SHALL
 APPLY.
 40.1.1.4 INDUSTRIAL OCCUPANCIES SHALL INCLUDE FACTORIES
 MAKING
 PRODUCTS OF ALL KINDS AND PROPERTIES USED FOR
 OPERATIONS SUCH AS
 PROCESSING, ASSEMBLING, MIXING, PACKAGING, FINISHING OR
 DECORATING, REPAIRING, AND SIMILAR OPERATIONS.
  
  
 1) THERE ARE NO INDICATIONS OF ILLUMINATION OF THE
 MEANS OF EGRESS
  
 40.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL
 BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8 OR WITH
 NATURAL
 LIGHTING THAT PROVIDES THE REQUIRED LEVEL OF
 ILLUMINATION IN
 STRUCTURES OCCUPIED ONLY DURING DAYLIGHT HOURS.
  
 7.8 ILLUMINATION OF MEANS OF EGRESS.
 7.8.1 GENERAL.
 7.8.1.1* ILLUMINATION OF MEANS OF EGRESS SHALL BE
 PROVIDED IN
 ACCORDANCE WITH SECTION 7.8 FOR EVERY BUILDING AND
 STRUCTURE WHERE
 REQUIRED IN CHAPTERS 11 THROUGH 43. FOR THE PURPOSES OF
 THIS
 REQUIREMENT, EXIT ACCESS SHALL INCLUDE ONLY DESIGNATED
 STAIRS, AISLES,
 CORRIDORS, RAMPS, ESCALATORS, AND PASSAGEWAYS LEADING
 TO AN EXIT. FOR THE
 PURPOSES OF THIS REQUIREMENT, EXIT DISCHARGE SHALL
 INCLUDE ONLY
 DESIGNATED STAIRS, AISLES, CORRIDORS, RAMPS,
 ESCALATORS, WALKWAYS, AND EXIT
 PASSAGEWAYS LEADING TO A PUBLIC WAY.
 7.8.1.2 ILLUMINATION OF MEANS OF EGRESS SHALL BE
 CONTINUOUS DURING THE
 TIME THAT THE CONDITIONS OF OCCUPANCY REQUIRE THAT THE
 MEANS OF EGRESS
 BE AVAILABLE FOR USE, UNLESS OTHERWISE PROVIDED IN
 7.8.1.2.2.
 7.8.1.2.1 ARTIFICIAL LIGHTING SHALL BE EMPLOYED AT SUCH
 LOCATIONS AND FOR
 SUCH PERIODS OF TIME AS ARE NECESSARY TO MAINTAIN THE
 ILLUMINATION TO THE
 MINIMUM CRITERIA VALUES HEREIN SPECIFIED.
  
 PLEASE REVIEW AND PROVIDE
  
  
  
 2) THERE ARE NO INDICATIONS OF EMERGENCY LIGHTING.
  
 40.2.9 EMERGENCY LIGHTING
 40.2.9.1 EMERGENCY LIGHTING SHALL BE IN ACCORDANCE WITH
 SECTION 7.9
 40.2.9.2 EMERGENCY LIGHTING SHALL NOT BE REQUIRED FOR
 ANY OF THE
 FOLLOWING:
 (1) SPECIAL-PURPOSE INDUSTRIAL OCCUPANCIES WITHOUT
 ROUTINE
 HUMAN HABITATION
 (2) STRUCTURES OCCUPIED ONLY DURING DAYLIGHT HOURS,
 WITH
 SKYLIGHTS OR WINDOWS ARRANGED TO PROVIDE THE REQUIRED
 LEVEL
 OF ILLUMINATION ON ALL PORTIONS OF THE MEANS OF EGRESS
 DURING
 SUCH HOURS
  
 7.9 EMERGENCY LIGHTING.
 7.9.1 GENERAL.
 7.9.1.1* EMERGENCY LIGHTING FACILITIES FOR MEANS OF
 EGRESS SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.9 FOR THE
 FOLLOWING:
 (1) BUILDINGS OR STRUCTURES WHERE REQUIRED IN CHAPTERS
 11 THROUGH 43
 (2) UNDERGROUND AND LIMITED ACCESS STRUCTURES AS
 ADDRESSED IN SECTION
 11.7
 (3) HIGH-RISE BUILDINGS AS REQUIRED BY OTHER SECTIONS
 OF THIS CODE
 (4) DOORS EQUIPPED WITH DELAYED-EGRESS LOCKS
 (5) STAIR SHAFTS AND VESTIBULES OF SMOKEPROOF
 ENCLOSURES, FOR WHICH THE
 FOLLOWING ALSO APPLY:
 (A) THE STAIR SHAFT AND VESTIBULE SHALL BE PERMITTED TO
 INCLUDE A
 STANDBY GENERATOR THAT IS INSTALLED FOR THE SMOKEPROOF
 ENCLOSURE MECHANICAL VENTILATION EQUIPMENT.
 (B) THE STANDBY GENERATOR SHALL BE PERMITTED TO BE USED
 FOR THE
 STAIR SHAFT AND VESTIBULE EMERGENCY LIGHTING POWER
 SUPPLY.
 (6) NEW ACCESS-CONTROLLED EGRESS DOORS IN ACCORDANCE
 WITH 7.2.1.6.2
  
 7.9.2 PERFORMANCE OF SYSTEM.
 7.9.2.1 EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A
 MINIMUM OF 1?
 HOURS IN THE EVENT OF FAILURE OF NORMAL LIGHTING.
 7.9.2.1.1 EMERGENCY LIGHTING FACILITIES SHALL BE
 ARRANGED TO PROVIDE
 INITIAL ILLUMINATION THAT IS NOT LESS THAN AN AVERAGE
 OF 1 FT-CANDLE (10.8
 LUX) AND, AT ANY POINT, NOT LESS THAN 0.1 FT-CANDLE
 (1.1 LUX) , MEASURED
 ALONG THE PATH OF EGRESS AT FLOOR LEVEL.
 7.9.2.1.2 ILLUMINATION LEVELS SHALL BE PERMITTED TO
 DECLINE TO NOT
 LESS THAN AN AVERAGE OF 0.6 FT-CANDLE (6.5 LUX) AND, AT
 ANY POINT,
 NOT LESS THAN 0.06 FT-CANDLE (0.65 LUX) AT THE END OF
 1? HOURS.
  
 7.9.2.3* THE EMERGENCY LIGHTING SYSTEM SHALL BE
 ARRANGED TO
 PROVIDE THE REQUIRED ILLUMINATION AUTOMATICALLY IN THE
 EVENT OF ANY
 INTERRUPTION OF NORMAL LIGHTING DUE TO ANY OF THE
 FOLLOWING:
 (1) FAILURE OF A PUBLIC UTILITY OR OTHER OUTSIDE
 ELECTRICAL POWER
 SUPPLY
 (2) OPENING OF A CIRCUIT BREAKER OR FUSE
 (3) MANUAL ACT(S), INCLUDING ACCIDENTAL OPENING OF A
 SWITCH
 CONTROLLING NORMAL LIGHTING FACILITIES
  
 7.9.2.6 EXISTING BATTERY-OPERATED EMERGENCY LIGHTS
 SHALL USE ONLY
 RELIABLE TYPES OF RECHARGEABLE BATTERIES PROVIDED WITH
 SUITABLE
 FACILITIES FOR MAINTAINING THEM IN PROPERLY CHARGED
 CONDITION.
 BATTERIES USED IN SUCH LIGHTS OR UNITS SHALL BE
 APPROVED FOR THEIR
 INTENDED USE AND SHALL COMPLY WITH NFPA 70, NATIONAL
 ELECTRICAL
 CODE.
 7.9.2.7 THE EMERGENCY LIGHTING SYSTEM SHALL BE EITHER
 CONTINUOUSLY
 IN OPERATION OR SHALL BE CAPABLE OF REPEATED AUTOMATIC
 OPERATION
 WITHOUT MANUAL INTERVENTION.
  
 PLEASE REVIEW AND PROVIDE.
  
  
  
 3) THERE IS NO INDICATION OF AN EXIT SIGN IN THE NEWLY
 CREATED SPACE AND WHEN A PERSON WOULD EXIT FROM THE NEW
 SPACE.
  
 40.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL
 HAVE SIGNS IN ACCORDANCE WITH SECTION 7.10.
  
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS.
 7.10.1.2.2* HORIZONTAL COMPONENTS OF THE EGRESS PATH
 WITHIN AN EXIT
 ENCLOSURE SHALL BE MARKED BY APPROVED EXIT OR
 DIRECTIONAL EXIT SIGNS
 WHERE THE CONTINUATION OF THE EGRESS PATH IS NOT
 OBVIOUS.
  
 7.10.1.5 EXIT ACCESS.
 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED,
 READILY
 VISIBLE SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO
 REACH THE EXIT IS
 NOT READILY APPARENT TO THE OCCUPANTS.
 7.10.1.5.2* NEW SIGN PLACEMENT SHALL BE SUCH THAT NO
 POINT IN AN
 EXIT ACCESS CORRIDOR IS IN EXCESS OF THE RATED VIEWING
 DISTANCE OR
 100 FT (30 M), WHICHEVER IS LESS, FROM THE NEAREST
 SIGN.
  
  
  
 4) THE TITLE HEADER INDICATES AN ADDRESS OF 935 35TH
 CT.
  
 IT SHOULD READ 25TH CT.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 5) THERE APPEARS TO BE A WINDOW WITHIN THE NEW WALL.
  
 THERE IS NO WINDOW SCHEDULE, SIZE, TYPE.
  
 PLEASE REVIEW AND PROVIDE WINDOW DETAILS.
  
  
  
 6) THERE IS NO INDICATIONS OF A DOOR SCHEDULE FOR THE
 NEW DOOR.
  
 THERE IS NO INDICATION OF THE SIZE, TYPE, AND HARDWARE
 FOR THE DOOR.
  
 40.2.2.2 DOORS.
 40.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
  
 40.2.2.2.4 LOCKS IN ACCORDANCE WITH 7.2.1.6.3 SHALL BE
 PERMITTED
  
 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES.
 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED
 READILY FROM
 THE EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED.
  
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A
 TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM
 THE EGRESS
 SIDE.
  
 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR
 LEAF SHALL
 BE PROVIDED WITH A RELEASING DEVICE THAT HAS AN OBVIOUS
 METHOD OF
 OPERATION AND THAT IS READILY OPERATED UNDER ALL
 LIGHTING CONDITIONS.
 7.2.1.5.10.1 THE RELEASING MECHANISM FOR ANY LATCH
 SHALL BE
 LOCATED AS FOLLOWS:
 (1) NOT LESS THAN 34 IN. (865 MM) ABOVE THE FINISHED
 FLOOR FOR
 OTHER THAN EXISTING INSTALLATIONS
 (2) NOT MORE THAN 48 IN. (1220 MM) ABOVE THE FINISHED
 FLOOR
 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN THE
 DOOR LEAF
 WITH NOT MORE THAN ONE RELEASING OPERATION, UNLESS
 OTHERWISE
 SPECIFIED IN 7.2.1.5.10.3, 7.2.1.5.10.4, OR
 7.2.1.5.10.6.
  
 PLEASE REVIEW AND PROVIDE DOOR AND HARDWARE DETAILS
 THAT COMPLY WITH NFPA 101 CH 7 MEANS OF EGRESS.
  
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  