| 2020-04-29 16:36:43 | PLAN REVIEW - ELECTRICAL |
| | |
| | CODES IN EFFECT: |
| | 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER ? BUILDING - PX3169 |
| | PLANS EXAMINER ? 1&2 FAMILY - SFP306 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | |
| | RESULTS: DENIED |
| | |
| | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| | BELOW. |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. SMOKE DETECTOR CANNOT BE WITHIN THREE FEET OF |
| | BATHROOM DOOR PER R314.3 |
| | |
| | R314.1 GENERAL. |
| | SMOKE ALARMS SHALL COMPLY WITH NFPA 72 AND SECTION |
| | R314. |
| | R314.3 LOCATION. |
| | SMOKE ALARMS SHALL BE INSTALLED IN THE FOLLOWING |
| | LOCATIONS: |
| | 1. 1.IN EACH SLEEPING ROOM. |
| | 2. 2.OUTSIDE EACH SEPARATE SLEEPING AREA IN THE |
| | IMMEDIATE VICINITY OF THE BEDROOMS. |
| | 3. 3.ON EACH ADDITIONAL STORY OF THE DWELLING, |
| | INCLUDING BASEMENTS AND HABITABLE ATTICS AND NOT |
| | INCLUDING CRAWL SPACES AND UNINHABITABLE ATTICS. IN |
| | DWELLINGS OR DWELLING UNITS WITH SPLIT LEVELS AND |
| | WITHOUT AN INTERVENING DOOR BETWEEN THE ADJACENT |
| | LEVELS, A SMOKE ALARM INSTALLED ON THE UPPER LEVEL |
| | SHALL SUFFICE FOR THE ADJACENT LOWER LEVEL PROVIDED |
| | THAT THE LOWER LEVEL IS LESS THAN ONE FULL STORY BELOW |
| | THE UPPER LEVEL. |
| | 4. 4.SMOKE ALARMS SHALL BE INSTALLED NOT LESS THAN 3 |
| | FEET (914 MM) HORIZONTALLY FROM THE DOOR OR OPENING OF |
| | A BATHROOM THAT CONTAINS A BATHTUB OR SHOWER UNLESS |
| | THIS WOULD PREVENT PLACEMENT OF A SMOKE ALARM REQUIRED |
| | BY SECTION R314.3 |
| | |
| | |
| | 2. EXISTING WINDOW AT HALL BATH WILL BE REMOVED AND |
| | OPENING CLOSED. PROVIDE MECHANICAL VENTILATION PER |
| | R303.3 |
| | |
| | R303.3BATHROOMS. |
| | BATHROOMS, WATER CLOSET COMPARTMENTS AND OTHER SIMILAR |
| | ROOMS SHALL BE PROVIDED WITH AGGREGATE GLAZING AREA IN |
| | WINDOWS OF NOT LESS THAN 3 SQUARE FEET (0.3 M2), |
| | ONE-HALF OF WHICH MUST BE OPENABLE. |
| | EXCEPTION: THE GLAZED AREAS SHALL NOT BE REQUIRED WHERE |
| | ARTIFICIAL LIGHT AND A LOCAL EXHAUST SYSTEM ARE |
| | PROVIDED. THE MINIMUM LOCAL EXHAUST RATES SHALL BE |
| | DETERMINED IN ACCORDANCE WITH SECTION M1507. EXHAUST |
| | AIR FROM THE SPACE SHALL BE EXHAUSTED DIRECTLY TO THE |
| | OUTDOORS. |
| | |
| | |
| | 3. INCLUDE EXHAUST FAN ON ELECTRICAL PLAN. INDICATE |
| | CIRCUT PROVIDING POWER ON SCHEDULE. |
| | |
| | |
| | |
| | |
| | |
| | |