Plan Review Notes
Plan Review Notes For Permit 20040663
Permit Number 20040663
Review Stop ASBESTOS
Sequence Number 1
Notes
Date Text
2020-04-21 12:52:37PLEASE SPECIFY ON PLANS FOR EACH SUBMITTAL WHAT WORK IS
 TO BE COMPLETED, AND PROVIDE DRAWINGS, AND MANUFACTURER
 SPECIFICATION SHEETS FOR MATERIALS USED.
  
 THE CONSTRUCTION OF THE BUILDING SHALL COMPLY WITH THE
 5TH EDITION OF THE FLORIDA FIRE PREVENTION CODE,
 INCLUDING NFPA 1 & 101, AND ALL ASSOCIATED FIRE CODES.
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY MORE OFTEN TO REDUCE THE
 ACCUMULATION OF POTENTIAL LIFE AND FIRE SAFETY HAZARDS.
  
 SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED
 EXTERIOR AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION
 AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE
 SMOKING IS PERMITTED, SAFE RECEPTACLES FOR SMOKING
 MATERIALS SHALL BE PROVIDED.
  
 PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 THE BUILDING ADDRESS SHALL BE CLEARLY VISIBLE FROM ALL
 ACCESS ROADWAYS, INCLUDING DURING CONSTRUCTION. ADDRESS
 NUMBERS SHALL CONTRAST WITH THEIR BACKGROUND AND SHALL
 NOT BE LESS THAN SIX (6) INCHES IN HEIGHT WITH A ONE
 (1) INCH STROKE FOR ALL BUILDINGS.
  
 31.3.4.5.1* IN BUILDINGS OTHER THAN THOSE EQUIPPED
 THROUGHOUT WITH AN EXISTING, COMPLETE AUTOMATIC SMOKE
 DETECTION SYSTEM, SMOKE ALARMS SHALL BE INSTALLED IN
 ACCORDANCE WITH 9.6.2.10, AS MODIFIED BY 31.3.4.5.2,
 OUTSIDE EVERY SLEEPING AREA IN THE IMMEDIATE VICINITY
 OF THE BEDROOMS AND ON ALL LEVELS OF THE DWELLING UNIT,
 INCLUDING BASEMENTS.
  
 31.3.4.1.1 APARTMENT BUILDINGS FOUR OR MORE STORIES IN
 HEIGHT OR WITH MORE THAN 11 DWELLING UNITS, OTHER THAN
 THOSE MEETING THE REQUIREMENTS OF 31.3.4.1.2, SHALL BE
 PROVIDED WITH
 A FIRE ALARM SYSTEM IN ACCORDANCE WITH SECTION 9.6,
 EXCEPT AS MODIFIED BY 31.3.4.2 THROUGH 31.3.4.5.
  