Plan Review Notes
Plan Review Notes For Permit 20040654
Permit Number 20040654
Review Stop E
Sequence Number 5
Notes
Date Text
2021-04-22 13:45:58ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) OUTLETS REQUIRED AT THR FRONT AND REAR OF UNIT
 210.52(E)(1)
  
 FOR A ONE-FAMILY DWELLING AND EACH UNIT OF A TWO-FAMILY
 DWELLING THAT IS AT GRADE LEVEL, AT LEAST ONE
 RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND NOT
 MORE THAN 2.0 M (6 1?2 FT) ABOVE GRADE LEVEL SHALL BE
 INSTALLED AT THE FRONT AND BACK OF THE DWELLING
  
 2) SMOKE ALARMS TO BE AT LEAST 6' AWAY FROM COOKING
 APPLIANCES R314 FBC
  
 3) OUTLET SPACING DOES NOT MEET CODE 210.52(A)(1)
  
 SPACING. RECEPTACLES SHALL BE INSTALLED SUCH THAT NO
 POINT MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY
 WALL SPACE IS MORE THAN 1.8 M (6 FT) FROM A RECEPTACLE
 OUTLET.
 ANY SPACE 600 MM (2 FT) OR MORE IN WIDTH (INCLUDING
 SPACE MEASURED AROUND CORNERS) AND UNBROKEN ALONG THE
 FLOOR LINE BY DOORWAYS AND SIMILAR OPENINGS,
 FIREPLACES, AND FIXED CABINETS THAT DO NO
  