| Plan Review Notes For Permit 20040645 |
| Permit Number |
20040645 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2020-05-15 09:40:22 | PERMIT #20040645 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PLANS DONT INDICATE ACCESS SWITCH FOR NEW INSTALL ENTRY | | | GATES FOR FIRE DEPARTMENT | | | | | | 18.2.2* ACCESS TO STRUCTURES OR AREAS. | | | 18.2.2.1 ACCESS BOX(ES). THE AHJ SHALL HAVE THE | | | AUTHORITY TO | | | REQUIRE AN ACCESS BOX(ES) TO BE INSTALLED IN AN | | | ACCESSIBLE LOCATION | | | WHERE ACCESS TO OR WITHIN A STRUCTURE OR AREA IS | | | DIFFICULT | | | BECAUSE OF SECURITY. THE ACCESS BOX(ES) SHALL BE OF AN | | | APPROVED | | | TYPE LISTED IN ACCORDANCE WITH UL 1037. | | | 18.2.2.2 ACCESS TO GATED SUBDIVISIONS OR DEVELOPMENTS. | | | THE | | | AHJ SHALL HAVE THE AUTHORITY TO REQUIRE FIRE DEPARTMENT | | | ACCESS | | | BE PROVIDED TO GATED SUBDIVISIONS OR DEVELOPMENTS | | | THROUGH | | | THE USE OF AN APPROVED DEVICE OR SYSTEM. | | | | | | BRITTANY WOODS | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4754 | | | | | | |
|