2020-05-15 09:40:22PERMIT #20040645
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLANS DONT INDICATE ACCESS SWITCH FOR NEW INSTALL ENTRY
 GATES FOR FIRE DEPARTMENT
  
 18.2.2* ACCESS TO STRUCTURES OR AREAS.
 18.2.2.1 ACCESS BOX(ES). THE AHJ SHALL HAVE THE
 AUTHORITY TO
 REQUIRE AN ACCESS BOX(ES) TO BE INSTALLED IN AN
 ACCESSIBLE LOCATION
 WHERE ACCESS TO OR WITHIN A STRUCTURE OR AREA IS
 DIFFICULT
 BECAUSE OF SECURITY. THE ACCESS BOX(ES) SHALL BE OF AN
 APPROVED
 TYPE LISTED IN ACCORDANCE WITH UL 1037.
 18.2.2.2 ACCESS TO GATED SUBDIVISIONS OR DEVELOPMENTS.
 THE
 AHJ SHALL HAVE THE AUTHORITY TO REQUIRE FIRE DEPARTMENT
 ACCESS
 BE PROVIDED TO GATED SUBDIVISIONS OR DEVELOPMENTS
 THROUGH
 THE USE OF AN APPROVED DEVICE OR SYSTEM.
  