| 2020-04-17 14:34:38 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | |
| | THE SUBMITTED PLANS LACK SPECIFIC DETAILS OF THIS |
| | OCCUPANCY THAT WILL CONFIRMED AND VERIFIED BY THE FIRE |
| | INSPECTOR DURING THE FIRE INSPECTION. |
| | |
| | PER THE 2015 FLORIDA FIRE PREVENTION CODE THIS IS A NEW |
| | RESIDENTIAL BOARD AND CARE OCCUPANCY. |
| | |
| | PATIENTS ARE NOT ALLOWED TO RESIDE UNTIL THE CONDITIONS |
| | AND REQUIRMENTS OF THE FIRE CODE ARE INSTALLED, TESTED |
| | AND INSPECTED. |
| | |
| | |
| | 1) THERE ARE NO INDICATIONS OF SOKE ALARMS |
| | |
| | PER NFPA 101, CH 32, NEW RESIDENTIAL BOARD AND CARE |
| | OCCUPANCIES |
| | |
| | 32.2.3.4.3.3 ADDITIONAL SMOKE ALARMS SHALL BE INSTALLED |
| | IN ALL |
| | LIVING AREAS, AS DEFINED IN 3.3.21.5. |
| | 32.2.3.4.3.4 EACH SLEEPING ROOM SHALL BE PROVIDED WITH |
| | AN |
| | APPROVED SMOKE ALARM IN ACCORDANCE WITH 9.6.2.10. |
| | |
| | 9.6.2.10.8* IN NEW CONSTRUCTION, WHERE TWO OR MORE |
| | SMOKE ALARMS |
| | ARE REQUIRED WITHIN A DWELLING UNIT, SUITE OF ROOMS, OR |
| | SIMILAR AREA, |
| | THEY SHALL BE ARRANGED SO THAT OPERATION OF ANY SMOKE |
| | ALARM SHALL |
| | CAUSE THE ALARM IN ALL SMOKE ALARMS WITHIN THE DWELLING |
| | UNIT, SUITE |
| | OF ROOMS, OR SIMILAR AREA TO SOUND, UNLESS OTHERWISE |
| | PERMITTED BY |
| | ONE OF THE FOLLOWING: |
| | (1) THE REQUIREMENT OF 9.6.2.10.8 SHALL NOT APPLY WHERE |
| | PERMITTED BY ANOTHER SECTION OF THIS CODE. |
| | (2) THE REQUIREMENT OF 9.6.2.10.8 SHALL NOT APPLY TO |
| | CONFIGURATIONS THAT PROVIDE EQUIVALENT DISTRIBUTION OF |
| | THE |
| | ALARM SIGNAL. |
| | 9.6.2.10.9 THE ALARMS DESCRIBED IN 9.6.2.10.8 SHALL |
| | SOUND ONLY |
| | WITHIN AN INDIVIDUAL DWELLING UNIT, SUITE OF ROOMS, OR |
| | SIMILAR AREA |
| | AND SHALL NOT ACTUATE THE BUILDING FIRE ALARM SYSTEM, |
| | UNLESS |
| | OTHERWISE PERMITTED BY THE AUTHORITY HAVING |
| | JURISDICTION. |
| | 9.6.2.10.10 SMOKE ALARMS SHALL BE PERMITTED TO BE |
| | CONNECTED TO |
| | THE BUILDING FIRE ALARM SYSTEM FOR THE PURPOSE OF |
| | ANNUNCIATION IN |
| | ACCORDANCE WITH NFPA 72. |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE. |
| | |
| | FIRE INSPECTOR WILL CONFIRM AND VERIFY ON FIRE |
| | INSPECTION. |
| | |
| | |
| | |
| | |
| | 2) THERE ARE NO INDCATIONS OF DOOR HARDWARE. |
| | |
| | 32.2.2.5.3 EVERY CLOSET DOOR LATCH SHALL BE READILY |
| | OPENED FROM |
| | THE INSIDE. |
| | 32.2.2.5.4 EVERY BATHROOM DOOR SHALL BE DESIGNED TO |
| | ALLOW |
| | OPENING FROM THE OUTSIDE DURING AN EMERGENCY WHEN |
| | LOCKED. |
| | 32.2.2.5.5 NO DOOR IN ANY MEANS OF ESCAPE, OTHER THAN |
| | THOSE |
| | MEETING THE REQUIREMENT OF 32.2.2.5.5.1, 32.2.2.5.5.2, |
| | OR |
| | 32.2.2.5.5.3, SHALL BE LOCKED AGAINST EGRESS WHEN THE |
| | BUILDING IS |
| | OCCUPIED |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE. |
| | |
| | FIRE INSPECTOR WILL CONFIRM AND VERIFY ON FIRE |
| | INSPECTION. |
| | |
| | |
| | |
| | 3) THERE IS NO IDNCATION OF DOOR SIZE TO BEDROOMS |
| | WITHIN CORRIDOR/HALLWAY THE |
| | |
| | 32.2.3.6 CONSTRUCTION OF CORRIDOR WALLS. |
| | 32.2.3.6.1 CORRIDOR WALLS, OTHER THAN THOSE MEETING THE |
| | PROVISIONS |
| | OF 32.2.3.6.2, SHALL MEET ALL OF THE FOLLOWING |
| | REQUIREMENTS: |
| | (1) WALLS SEPARATING SLEEPING ROOMS SHALL HAVE A |
| | MINIMUM ?- |
| | HOUR FIRE RESISTANCE RATING. THE MINIMUM ?-HOUR FIRE |
| | RESISTANCE RATING SHALL BE CONSIDERED TO BE ACHIEVED IF |
| | THE |
| | PARTITIONING IS FINISHED ON BOTH SIDES WITH LATH AND |
| | PLASTER OR |
| | MATERIALS PROVIDING A 15-MINUTE THERMAL BARRIER. |
| | (2) SLEEPING ROOM DOORS SHALL BE SUBSTANTIAL DOORS, |
| | SUCH AS THOSE |
| | OF 1? IN. (44 MM) THICK, SOLID-BONDED WOOD-CORE |
| | CONSTRUCTION |
| | OR OF OTHER CONSTRUCTION OF EQUAL OR GREATER STABILITY |
| | AND FIRE |
| | INTEGRITY. |
| | |
| | PLEASE REVIEW AND ENSURE COMPLIANCE. |
| | |
| | FIRE INSPECTOR WILL CONFIRM AND VERIFY ON FIRE |
| | INSPECTION. |
| | |
| | |
| | |
| | 4) THERE IS NO INDICATION OF HOW MANY RESIDENTS ARE |
| | PROPOSED |
| | |
| | MORE THAN 6 WILL REQUIRE A FIRE ALARM AND MAY REQUIRE A |
| | FIRE SPRINKLER SYSTEM. |
| | |
| | PER FL STATUTUE 419 COMMUNITY RESIDENTIAL HOMES |
| | |
| | (2)?HOMES OF SIX OR FEWER RESIDENTS WHICH OTHERWISE |
| | MEET THE DEFINITION OF A COMMUNITY RESIDENTIAL HOME |
| | SHALL BE DEEMED A SINGLE-FAMILY UNIT AND A |
| | NONCOMMERCIAL, RESIDENTIAL USE FOR THE PURPOSE OF LOCAL |
| | LAWS AND ORDINANCES. |
| | |
| | UNDER 6 THE OCCUPANCY IS CONSDERED A RESIDENTIAL HOME |
| | AND WOULD NOT REQUIRE A FIRE ALARM OF SPRINKLER, SMOKE |
| | ALARMS AND FIRE EXTINGUSHERS WOULD BE REQUIRED. |
| | |
| | HOWEVER, MORE THAN 6 REQUIRES A FIRE ALARM AND MAY |
| | REQUIRE A FIRE SPRINKLER SYSTEM PER NFPA 101, CH 32 |
| | RESIDENTIAL BOARD AND CARE OCCUPANCIES |
| | |
| | 32.2.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 32.2.3.4.1 GENERAL. A MANUAL FIRE ALARM SYSTEM SHALL BE |
| | PROVIDED |
| | IN ACCORDANCE WITH SECTION 9.6. |
| | 32.2.3.4.2 OCCUPANT NOTIFICATION. OCCUPANT NOTIFICATION |
| | SHALL BE |
| | PROVIDED AUTOMATICALLY, WITHOUT DELAY, IN ACCORDANCE |
| | WITH 9.6.3. |
| | |
| | 32.2.3.5* EXTINGUISHMENT REQUIREMENTS. |
| | 32.2.3.5.1* ALL FACILITIES, OTHER THAN THOSE MEETING |
| | THE |
| | REQUIREMENT OF 32.2.3.5.2, SHALL BE PROTECTED |
| | THROUGHOUT BY AN |
| | APPROVED AUTOMATIC SPRINKLER SYSTEM, INSTALLED IN |
| | ACCORDANCE WITH |
| | 32.2.3.5.3, USING QUICK-RESPONSE OR RESIDENTIAL |
| | SPRINKLERS. |
| | 32.2.3.5.2* IN CONVERSIONS, SPRINKLERS SHALL NOT BE |
| | REQUIRED IN |
| | SMALL BOARD AND CARE HOMES SERVING EIGHT OR FEWER |
| | RESIDENTS WHEN |
| | ALL OCCUPANTS HAVE THE ABILITY AS A GROUP TO MOVE |
| | RELIABLY TO A |
| | POINT OF SAFETY WITHIN 3 MINUTES. |
| | |
| | PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE A WRITTEN |
| | LETTER CONFIMRING THE NUMBER OF RESIDENTS TO THE FIRE |
| | INSPECTOR AN FIRE INSPECTIONS. |
| | |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| 2020-04-14 17:13:50 | F/A WILL BE BY SEPARATE PERMIT. |