2020-07-08 15:02:403RD REVIEW FBC-2017 PLUMBING
 PERMIT #20040614
 7/8/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 PLAN REVIEW RESULTS: DENIED.
  
 1) P1: PLEASE PROVIDE THE SCOPE OF WORK FOR THE WATER
 HEATER- LABEL IT AS EITHER NEW, EXISTING, RELOCATED-
 SECTION 107.2.1 WPB. AN EQUIPMENT SCHEDULE IS REQUIRED
 FOR NEW WATER HEATERS. THE SCHEDULE SHALL INDICATE MAKE
 AND MODEL NUMBER, GALLON SIZE, AND EFFICIENCY RATING-
 SEE TABLE C404.2 FBC EC. THE DETAIL SHOWS THE PAN DRAIN
 LINE TO DISCHARGE INTO THE NEAREST SANITARY DRAIN WHICH
 IS NOT AN APPROVED LOCATION. THIS MAY BE A TYPO AND
 THERE IS ACCESS TO THE BUILDING STORM DRAIN RISER IN
 THE CLOSET- SECTION 504.7.2 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  