| 2020-07-08 15:02:40 | 3RD REVIEW FBC-2017 PLUMBING |
| | PERMIT #20040614 |
| | 7/8/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) P1: PLEASE PROVIDE THE SCOPE OF WORK FOR THE WATER |
| | HEATER- LABEL IT AS EITHER NEW, EXISTING, RELOCATED- |
| | SECTION 107.2.1 WPB. AN EQUIPMENT SCHEDULE IS REQUIRED |
| | FOR NEW WATER HEATERS. THE SCHEDULE SHALL INDICATE MAKE |
| | AND MODEL NUMBER, GALLON SIZE, AND EFFICIENCY RATING- |
| | SEE TABLE C404.2 FBC EC. THE DETAIL SHOWS THE PAN DRAIN |
| | LINE TO DISCHARGE INTO THE NEAREST SANITARY DRAIN WHICH |
| | IS NOT AN APPROVED LOCATION. THIS MAY BE A TYPO AND |
| | THERE IS ACCESS TO THE BUILDING STORM DRAIN RISER IN |
| | THE CLOSET- SECTION 504.7.2 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |