| 2020-06-22 15:38:12 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT #20040614 |
| | 6/22//2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEETS A0, A1, & P1: THE REVISED PLANS SHOW BATHTUB |
| | TO SHOWER CONVERSIONS IN THE BATHROOMS. COMPLIANCE WITH |
| | THE FAIR HOUSING ACCESSIBILITY GUIDELINES IS REQUIRED. |
| | BECAUSE THE BUILDING WAS CONSTRUCTED IN ACCORDANCE WITH |
| | THE ACCESSIBILITY REQUIREMENTS OF THE FAIR HOUSING ACT |
| | AND THE DESIGN GUIDELINES FOR USABLE BATHROOMS IN |
| | DWELLING UNITS, THE ALTERATIONS THAT ARE PROPOSED IN |
| | THE BATHROOMS SHALL ALSO BE IN COMPLIANCE WITH THE FAIR |
| | HOUSING ACT. THE FAIR HOUSING ACCESSIBILITY GUIDELINES |
| | ARE INCLUDED IN THE FLORIDA ACCESSIBILITY CODE- 2017 |
| | SIXTH EDITION. COMPLIANCE WITH THE GUIDELINES REQUIRES |
| | THAT CLEAR FLOOR SPACES FOR WHEELCHAIR APPROACHES TO |
| | BATH FIXTURES SHALL EITHER BE MAINTAINED AS ORIGINALLY |
| | DESIGNED OR PROVIDED WHERE NEW FIXTURES ARE BEING |
| | INSTALLED. BASED ON THE DRAWINGS IT IS NOT CLEAR IF |
| | USUABLE BATHROOM TYPE A OR B WAS CHOSEN AS THE ORIGINAL |
| | DESIGN. THE DESIGNER OF RECORD MUST INDICATE WHCH TYPE |
| | DESIGN WAS USED ON THE PLAN, AND THEN PROVIDE ENLARGED |
| | DIMENSIONED DRAWINGS OF THE BATHROOMS WITH CLEAR FLOOR |
| | SPACE DIAGRAMS CONFIGURED FOR THE SHOWERS. PLEASE SEE |
| | REQUIREMENT 7 CONTAINED IN THE GUIDELINES AND FIGURE 5, |
| | AND FIGURES 7A, 7C, & 7D FOR GUIDANCE. REINFORCEMENTS |
| | FOR FUTURE GRAB BAR AND WALL HUNG BENCH SEAT |
| | INSTALLATIONS ARE ALSO REQUIRED. PROVIDE DIMENSIONED |
| | ELEVATION VIEWS AND DETAILS SHOWING THE LOCATIONS OF |
| | THE WALL REINFORCEMENTS. |
| | |
| | 1A) AS AN ALTERNATIVE TO MEETING THE GUIDELINES FOR THE |
| | BATH ALTERATIONS, THE OWNER AND DESIGNER OF RECORD FOR |
| | THE PROPOSED PROJECT MAY PROVIDE A SIGNED AND NOTARIZED |
| | AFFIDAVIT WHICH WOULD INDICATE ACKNOWLEDGEMENT THAT THE |
| | PROPOSED DESIGN DOES NOT MEET THE REQUIREMENTS OF THE |
| | FAIR HOUSING ACCESSIBILITY GUIDELINES, BUT WILL ALSO |
| | REQUIRE THE OWNER TO AGREE TO REVERT THE UNIT BACK TO |
| | COMPLIANCE AT TIME OF SALE IF SO REQUESTED BY THE |
| | BUYER. IF THIS OPTION IS CHOSEN, PLEASE SEND AN EMAIL |
| | TO [email protected] AND I WILL SEND A COPY OF THE FAIR |
| | HOUSING AFFIDAVIT. IF CHOOSING THIS OPTION IT WOULD BE |
| | ADVISABLE AT A MINIMUM TO INSTALL THE SHOWER WALL |
| | REINFORCEMENTS. |
| | |
| | 2) SHEET P1: CONCERNING THE SHOWER DRAIN OUTLETS, SHOW |
| | COMPLIANCE WITH ITEMS A, B, & C LISTED BELOW. |
| | |
| | A) REFER TO SECTION 1002.1 FBC P: THE HORIZONTAL |
| | DISTANCE FROM THE CENTERLINE OF THE NEW SHOWER DRAIN |
| | OUTLET TO THE CENTERLINE OF THE INLET OF THE EXISTING |
| | TRAPS SHALL NOT EXCEED 30". PLEASE PLACE A NOTE ON THE |
| | PLAN INDICATING COMPLIANCE. |
| | B) RELOCATING THE SHOWER DRAIN OUTLETS WILL REQUIRE THE |
| | FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE REINFORCING |
| | STEEL OR POST STRESSED FLOOR TENDONS. PLEASE PLACE A |
| | NOTE ON THE PLANS TO VERIFY COMPLIANCE WILL BE MET- |
| | SECTION 1-07.2.1 WPB. |
| | C) NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB |
| | WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE |
| | AROUND THE PIPING. PROVIDE A UL TESTED AND APPROVED |
| | FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION |
| | 714.4.1.2 FBC B. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |