Plan Review Notes
Plan Review Notes For Permit 20040614
Permit Number 20040614
Review Stop P
Sequence Number 1
Notes
Date Text
2020-04-30 14:39:35 
 1ST REVIEW FBC-2017 PLUMBING
 PERMIT #20040614
 4/30/2020
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A SANITARY ISOMETRIC DRAWING FOR THE
 RELOCATED KITCHEN SINK AND DISHWASHING MACHINE- SECTION
 107.3.5.1.3 WPB AMENDMENTS TO THE FBC-17.
  
 2) PROVIDE A WATER RISER DRAWING FOR THE RELOCATED SINK
 AND DISHWASHING MACHINE- SECTION 107.3.5.1.3 WPB
 AMENDMENTS TO THE FBC-17. PLEASE NOTE THAT A WATER
 HAMMER ARRESTOR IS REQUIRED FOR THE WATER SUPPLY LINE
 TO THE DISHWASHER- SECTION 604.9 FBC P; AND THE SUPPLY
 LINE SHALL BE PROTECTED AGAINST BACKFLOW BY EITHER AN
 AIR GAP OR A BACKFLOW PREVENTER- SECTION 409.2 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  