| Date |
Text |
| 2020-04-30 14:39:35 | |
| | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT #20040614 |
| | 4/30/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) PROVIDE A SANITARY ISOMETRIC DRAWING FOR THE |
| | RELOCATED KITCHEN SINK AND DISHWASHING MACHINE- SECTION |
| | 107.3.5.1.3 WPB AMENDMENTS TO THE FBC-17. |
| | |
| | 2) PROVIDE A WATER RISER DRAWING FOR THE RELOCATED SINK |
| | AND DISHWASHING MACHINE- SECTION 107.3.5.1.3 WPB |
| | AMENDMENTS TO THE FBC-17. PLEASE NOTE THAT A WATER |
| | HAMMER ARRESTOR IS REQUIRED FOR THE WATER SUPPLY LINE |
| | TO THE DISHWASHER- SECTION 604.9 FBC P; AND THE SUPPLY |
| | LINE SHALL BE PROTECTED AGAINST BACKFLOW BY EITHER AN |
| | AIR GAP OR A BACKFLOW PREVENTER- SECTION 409.2 FBC P. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |