| 2020-04-22 16:30:09 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #20040596 |
| | 4/22/20 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M0.1 NOTES 7 A. & B: THE PLANS SHOW FLEX DUCTS |
| | BUT THE SPECIFICATIONS FOR THE DUCTS WAS REMOVED FROM |
| | THE REVISED PLAN SHEET- SECTION 107.2.1 WPB. |
| | |
| | 2) M2.1 NOTE #5: SHOW THE REQUIRED FIRE/SMOKE DAMPER AT |
| | THE PENETRATION OF THE O/A DUCT AT THE SHAFT- SECTION |
| | 607.5.5 FBC M. CORRECT THE NOTE INDICATING O/A FOR |
| | RESTROOM EXHAUST- SECTION 107.2.1 WPB. |
| | |
| | 3) M2.1: PROVIDE O/A TO THE HP-2 SYSTEM SUPPLYING |
| | OFFICES 734, 735, 736- SECTION 403.3 FBC M. |
| | |
| | 4) M2.2 NOTE #4: SHOW THE REQUIRED FIRE/SMOKE DAMPER AT |
| | THE PENETRATION OF THE RESTROOM EXHAUST DUCT AT THE |
| | SHAFT- SECTION 607.5.5 FBC M. |
| | |
| | 5) M2.2: PROVIDE A THERMOSTAT FOR THE NEW AHU-1 SYSTEM |
| | IN THE IT 715 ROOM- SECTION C403.2.4.1 FBC EC. |
| | |
| | 6) M2.2: SHOW THE LOCATION OF THE CHASE FOR THE NEW |
| | REFRIGERANT LINES- SECTION 107.2.1 PROVIDE A NOTE TO |
| | INDICATE THE NEW SYSTEM AND REFRIGERANT LINES WILL |
| | INSTALLED PER MANUFACTURER'S SPECIFICATIONS- SECTION |
| | 304.1 FBC M. |
| | |
| | 7) M7.1: SHOW THE LOCATION OF THE NEW AC CONDENSER- |
| | SECTION 107.2.1 WPB. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |