2020-04-16 10:28:51THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) SHEET D 2 - UNDER GENERAL NOTES # 1 THERE IS AN
 INDICATION OF THIS IS A 3 STORY ALF.
  
 PLEASE CORRECT.
  
  
  
 2) SHEET D 2 - UNDER GENERAL NOTES # 2 & ALL TITLE
 HEADERS THERE ARE INDICATIONS OF THE ADDRESS OF 360
 PEMBROKE PLACE
  
 THE ADDRESS APPEARS TO BE 351 PEMBROKE.
  
 PLEASE REVIEW AND PROVIDE THE CORRECT ADDRESS IN ALL
 PLACES.
  
  
  
 3) SHEET D 2 - UNDER GENERAL NOTES # 8 THERE IS AN
 INDICATION OF A RISER AS 2-HR SURVIVALBILTIY.
  
 HOW IS THIS PROVIDED/CONSTRUCTED AND WHERE WILL THE
 VERTICAL CABLEING BE LOCATED.
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
  
  
 4) FOR TESTING AND COMPLIANCE PURPOSES WITH PALM BEACH
 COUNTY EMERGENCY COMMUNICATIONS YOU SHALL MAKE CONTACT
 AND
 COORDINATE WITH MARK FILLA, PALM BEACH COUNTY, PUBLIC
 SAFETY RADIO SYSTEMS MANAGER, FOR ALL RADIO SIGNAL
 DETAILS, OUTBOUND
 SIGNAL STRENGTH, ANTENNA DIRECTION AND TESTING BEFORE
 THE SYSTEM GOES LIVE, AS OUR RADIOS OPERATE ON THAT
 SYSTEM.
  
 [email protected] 561-233-0837
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGEMENT.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  