Plan Review Notes
Plan Review Notes For Permit 20040509
Permit Number 20040509
Review Stop E
Sequence Number 2
Notes
Date Text
2020-06-10 15:50:57CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION,
 PART VIII ELECTRICAL
 NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) I SEE THE 20A CIRCUIT FEEDING THE ATM, BUT NOT THE
 POWER.
  
 WHERE MORE THAN ONE BRANCH CIRCUIT OR FEEDER FEEDS A
 STRUCTURE A PANEL SHALL BE INSTALLED AND THE BRANCH
 CIRCUITS SHALL BE FED OF SAID PANEL.
  
 225.30 NUMBER OF SUPPLIES A BUILDING OR O THER
 STRUCTURE THAT IS SERVED BY A BRANCH CIRCUIT OR FEEDER
 ON THE LOAD SIDE OF A SERVICE DISCONNECTING MEANS SHALL
 BE SUPPLIED BY ONLY ONE FEEDER OR BRANCH CIRCUIT UNLESS
 PERMITTED IN 225.30(A) THROUGH (E). FOR THE PURPOSE OF
 THIS SECTION, A MULTIWIRE BRANCH CIRCUIT SHALL BE
 CONSIDERED A SINGLE CIRCUIT.
  
 2) FOR SEPARATE STRUCTURE A GROUNDING ELECTRODE SYSTEM
 SHALL BE INSTALLED. 250.32
  
 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A FEEDER(S)
 OR BRANCH CIRCUIT(S) (A) GROUNDING ELECTRODE.
 BUILDING(S) OR STRUCTURE(S) SUPPLIED BY FEEDER(S) OR
 BRANCH CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR
 GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE WI
 TH PART III OF ARTICLE 250. THE GROUNDING ELECTRODE
 CONDUCTOR(S) SHALL BE CON NECTED IN ACCORDANCE WITH
 250.32(B) OR (C). WHERE THERE IS NO EXISTING GROUNDING
 ELECTRODE, THE GROUNDING ELECTRODE(S) REQUIRED IN
 250.50 SHALL BE INSTALLED
  