2020-04-20 12:37:551ST REVIEW FBC-2017 PLUMBING
 PERMIT #20040506
 4/20/2020
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 NFPA 30
  
 1) SHEETS P1.01 SHOW THE LOCATIONS OF THE REMOTE FILL
 PIPE AND SMART PUMP, AND SHOW THE FILL PIPE RUN TO THE
 FUEL TANK- SECTION 1305.6 FBC M.
  
 2) P1.01: REFERENCE IS MADE TO SHEET P4.01A FOR VENT
 PIPING TERMINATION LOCATION. PLEASE UPLOAD THE MISSING
 PLAN SHEET- SECTION 1305.7 FBC M, AND SECTION 107.2.1
 WPB. THE PLANS SHALL SHOW THE NORMAL AND EMERGENCY
 RELIEF VENT PIPING TERMINATION LOCATIONS AT THE
 EXTERIOR OF THE BUILDING WITH REQUIRED CLEARANCES.
  
 3) PROVIDE A SUBMITTAL PACKAGE THAT INCLUDES PRODUCT
 SPECS FOR THE FUEL PIPING, FITTINGS AND VALVES,
 FLEXIBLE CONNECTORS AND HOSES, SMART PUMP, CONTROL
 DEVICES AND ALARMS- SEE SECTION 1302 FBC M, AND SECTION
 27.4 NFPA 30.
  
 4) PROVIDE PIPE ASSEMBLY AND INSTALLATION DETAILS AND
 SPECIFICATIONS- SECTION 1303 FBC M.
  
 PLAN REVIEW RESULTS: DENIED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  