| 2020-04-17 08:58:09 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | PLEASE SUBMIT A COMPLETE PACKAGE FOR THIS REVIEW. THERE |
| | ARE NOTES ON SHEET P5.03 THAT REFERENCE THE MECHANICAL |
| | SHEETS AND ?REFER TO PLANS FOR SIZES ?ROUTE PIPING FULL |
| | SIZE, REDUCED AT EQUIPMENT CONNECTION? PROVIDE PIPE |
| | MATERIAL RATED FOR THE SYSTEM, INFORMATION ON APPROVED |
| | FITTINGS AND VALVES FOR THE FUEL TYPE, PIPING DETAIL |
| | DRAWING INCLUDING ALL SUPPORTS, FUEL OIL VALVES FOR THE |
| | GENERATOR. PLEASE PROVIDE EXHAUST AND VENTING DETAILS |
| | FOR THE GENERATOR AND GENERATOR ROOM. PLEASE REFER TO |
| | FBC M CHAPTER 13 FOR FUEL OIL PIPING. FBC FS 107.2.1 |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| | SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| | SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| | THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| | PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| | PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| | UPDATED. |
| | |
| | |