2020-08-28 16:04:21COMMENTS FROM DERM:
  
 1) THE TANK SCHEMATIC "ENGINE OR DAY TANK SUPPLY"
 (ATTACHMENT 1086 GEN. FUEL TANK (R4)_TLC ?); THE SUPPLY
 LINE REQUIRES AN ANTISIPHON DEVICE IF THE END DIPS
 BELOW THE TOP OF TANK. THE ORDER OF COMPONENTS COMING
 FROM TOP OF TANK ARE 1ST THE BLOCK VALVE THEN
 ANTISIPHON DEVICE.
 2) THE RETURN LINE; IF IT IS CAPABLE OF SIPHONING THE
 TANK; IT COULD HAVE A BLEEDER HOLE AS THE PLANS STATE
 THE TANK FILL LINE WILL HAVE. (I DON'T REGULARLY SEE
 RETURN LINES THAT RUN TO BOTTOM OF SUPPLY TANK WITH
 DIFFUSERS).
 3) I COULD NOT TELL, BUT TANKS MAIN PRIMARY VENT MUST
 BE VENTED OUTSIDE
 4) OFTEN MISSED: TANK ROOMS REQUIRE A 4? CURB AT DOOR
 OPENINGS (PREVENTS A FUEL RELEASE FLOWING DOWN
 HALLWAYS)
  
  TANK SECONDARY MUST BE TESTED AFTER INSTALLATION;
 ALONG WITH OVERFILL PROTECTION DEVICE AND LEAK
 DETECTION DEVICES.
  WERE GIVEN 30 DAY NOTICE OF INSTALLATIONS, THE 48-72
 HRS PRIOR TO WORK SO WE CAN SCHEDULE AN INSPECTION.
  