| 2020-08-28 16:04:21 | COMMENTS FROM DERM: | | | | | | 1) THE TANK SCHEMATIC "ENGINE OR DAY TANK SUPPLY" | | | (ATTACHMENT 1086 GEN. FUEL TANK (R4)_TLC ?); THE SUPPLY | | | LINE REQUIRES AN ANTISIPHON DEVICE IF THE END DIPS | | | BELOW THE TOP OF TANK. THE ORDER OF COMPONENTS COMING | | | FROM TOP OF TANK ARE 1ST THE BLOCK VALVE THEN | | | ANTISIPHON DEVICE. | | | 2) THE RETURN LINE; IF IT IS CAPABLE OF SIPHONING THE | | | TANK; IT COULD HAVE A BLEEDER HOLE AS THE PLANS STATE | | | THE TANK FILL LINE WILL HAVE. (I DON'T REGULARLY SEE | | | RETURN LINES THAT RUN TO BOTTOM OF SUPPLY TANK WITH | | | DIFFUSERS). | | | 3) I COULD NOT TELL, BUT TANKS MAIN PRIMARY VENT MUST | | | BE VENTED OUTSIDE | | | 4) OFTEN MISSED: TANK ROOMS REQUIRE A 4? CURB AT DOOR | | | OPENINGS (PREVENTS A FUEL RELEASE FLOWING DOWN | | | HALLWAYS) | | | | | | TANK SECONDARY MUST BE TESTED AFTER INSTALLATION; | | | ALONG WITH OVERFILL PROTECTION DEVICE AND LEAK | | | DETECTION DEVICES. | | | WERE GIVEN 30 DAY NOTICE OF INSTALLATIONS, THE 48-72 | | | HRS PRIOR TO WORK SO WE CAN SCHEDULE AN INSPECTION. | | | | | | PBCDERM TANK INSPECTOR: JONATHAN ARLINE | | | SENIOR ENVIRONMENTAL ANALYST | | | PALM BEACH COUNTY DEPT. ENVIRONMENTAL RESOURCES | | | MANAGEMENT / STORAGE TANK REGULATION | | | 2300 NORTH JOG RD., 4TH FLOOR, WEST PALM BCH., FL | | | 33411-2743 | | | TEL. (561)-233-2535. FAX: (561) 233 2414 / E-MAIL: | | | [email protected] | | | | | | | | | |
|