| 2020-05-04 16:09:10 | |
| | 3RD REVIEW FBC-2017 FUEL GAS |
| | PERMIT #20040499 |
| | 5/4/202 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET P003: THE 2" UG LINE IS UNDERSIZED FOR A GAS |
| | LOAD OF 7428- MBH AT 153 FT. TOTAL DEVELOPED LENGTH. |
| | USING TABLE 404.4(22) AS NOTED IN THE RISER DRAWING, |
| | THE 2" LINE WILL PROVIDE A MAXIMUM OF 7290- MBH AT 150' |
| | TOTAL LENGTH. |
| | 2) AS REQUESTED IN THE PREVIOUS REVIEW, PROVIDE THE |
| | "PIPE LENGTH AND SIZE FOR LOW PRESSURE GAS TO |
| | GENERATOR". |
| | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE RETORTS |
| | AND EXHAUST STACKS, AND PROVIDE AN EXHAUST STACK |
| | DIAGRAM THAT INDICATES THE TYPE AND SIZE OF STACK, |
| | TOTAL LENGTH OF RUN, CLEARANCE TO COMBUSTIBLES, EXHAUST |
| | DISCHARGE CLEARANCES, AND METHOD OF SUPPORT ABOVE THE |
| | ROOF- SECTION 606.1 FBC FG. PLEASE NOTE I DID NOT SEE |
| | ANY SPECS OR VENTING DIAGRAM IN THE APPROVED PLANS |
| | UNDER PERMIT #19070081. |
| | 4) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE RETORTS |
| | AND SHOW HOW THE AIR IS BEING PROVIDED- SECTION 304.1 |
| | FBC FG |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |