| 2020-04-14 14:20:35 | REVIEWED BY JERRY SMITH. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | NFPA 54 = NATIONAL FUEL GAS CODE |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20040499 5801 GREENWOOD AVE |
| | MASTER PERMIT 19070081 |
| | |
| | GAS COMMENTS: DENIED |
| | 1. RE: GENERATOR; PER WPB FBC 107.2.1, IDENTIFY |
| | REGULATOR AND PROVIDE TABLE, PIPE LENGTH AND SIZE FOR |
| | LOW PRESSURE GAS TO GENERATOR. |
| | 2. PER WPB FBC 107.2.1, SHOW LENGTH OF PIPING FROM |
| | METER TO TEE, FROM TEE TO LP REGULATOR AHEAD OF RETORTS |
| | AND FROM TEE TO LP REGULATOR AT GENERATOR. |
| | 3. P101 STATES SEE SITE DRAWING FOR PIPING CONTINUATION |
| | TO GENERATOR. PER WPB FBC 107.2.1 PROVIDE THE SAME. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS |
| | REQUIRED BY FAC AND FS. |
| | ALL PLANS TO BE DIGITALLY SIGNED AND SEALED BY THE |
| | DESIGNER IN ACCORDANCE WITH FAC AND FS. |
| | |
| | |
| | |