| Plan Review Notes For Permit 20040453 |
| Permit Number |
20040453 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-04-16 09:01:07 | 1) A CLEAR AND LEGIBLE SANITARY RISER DIAGRAM SHALL BE | | | SUBMITTED SHOWING ALL PIPE SIZES, CONNECTION POINTS TO | | | EXISTING PIPING, THE TYPE OF ADAPTERS USED FOR THE | | | CONNECTIONS TO EXISTING PIPE, AND THE LOCATIONS OF | | | REQUIRED CLEANOUTS. | | | 2) THE AREA ABOVE GRADE WHERE THE TUNNEL WAS DUG SHALL | | | BE TREATED FOR TERMITES PER THE FBC-BUILDING SEC.1816.1 | | | OR FBC-RESIDENTIAL SEC. R318. A TERMITE CERTIFICATE | | | SHALL BE ONSITE FOR FINAL INSPECTION. THE AREA TO BE | | | TREATED SHALL EXTEND FOUR FEET ON EACH SIDE OF THE | | | EXCAVATION, THREE FEET OUT FROM THE BUILDING WALL AND | | | TWO FEET UP THE BUILDING WALL. | | | 3) HOW ARE THE PIPE BRACKETS BEING ATTACHED TO THE | | | WALL? INDICATE TYPE OF FASTENERS.WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 4) INDICATE ON THE PLANS HOW THE PIPE STANCIONS WILL BE | | | PROTECTED AGAINST CORROSION.WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | 5) MANUFACTURER'S SPECIFICATIONS FOR THE BRACKET AND | | | STANCION SHALL BE ON THE JOBSITE. | | | | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|