| 2020-04-14 15:12:06 | 2017 FBC- BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 20040431 |
| | ADD: 1601 S. FLAGLER DR. SUITE: 209-O |
| | CONT: EXCELL TILE CORP. |
| | TEL: 561-818-1955 |
| | E-MAIL: [email protected] |
| | |
| | 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION. |
| | |
| | 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: TUES. APRIL 14TH/ 2020 |
| | ACTION: DENIED |
| | |
| | 1) THE FLOOR PLAN THAT WAS SUBMITTED DOES NOT INDICATE |
| | OWNERSHIP OF WHO DREW THE PLAN. 2017 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATIVE CODE SECTION 107.3.4.3 CERTIFICATION BY |
| | CONTRACTOR. PLEASE NOTE THE EXCEPTION TO ENGINEERED |
| | PLANS UNDER 471.003(H) ELECTRICAL/ PLUMBING/ |
| | MECHANICAL, 481.229(1)(C) (BUILDING) REQUIRES THE |
| | CONTRACTOR TO BE LICENSED IN THE TRADE THAT THEY WILL |
| | BE CREATING THE PLANS TO BE SUBMITTED TO THE BUILDING |
| | DEPARTMENT. FOR EACH TRADE THE CONTRACTOR RESPONSIBLE |
| | FOR THE PLAN MUST PRINT THEIR NAME, SIGN THEIR NAME AND |
| | LICENSE NUMBER. |
| | |
| | 2) THE TEST DOCUMENT IS ONLY ONE PAGE, WE REQUIRE THE |
| | WHOLE TEST DOCUMENTS FOR ALL OF THE 3 REQUIRED TEST. |
| | PLEASE NOTE THERE IS ONLY ONE COMPANY THAT SELLS CORK |
| | THAT HAS BROUGHT IN TESTING FOR FLAME SPREAD. PLEASE |
| | ALSO IDENTIFY HOW MANY FLOORS ARE IN THIS BUILDING, AND |
| | WHAT TYPE OF STRUCTURAL FLOOR SYSTEM THIS BUILDING HAS. |
| | FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| | NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| | ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| | QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| | 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS (NOT SALES BROCHURES) |
| | SHOWING COMPLIANCE WITH ALL 3 REQUIREMENTS: |
| | |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| | 2017) |
| | |
| | 2A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.SHEET |
| | |
| | 2B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS, |
| | PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| | AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| | 90. |
| | |
| | 2C)(1) TYPE I OR II BUILDINGS. FLAME SPREAD- FBC-B 2017 |
| | 603.1. EXCEPTION 2. INSULATION INSTALLED BETWEEN A |
| | FINISHED FLOOR AND SOLID DECKING WITHOUT INTERVENING |
| | AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX |
| | OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 2C)(2) TYPE III-TYPE V CONSTRUCTION: FBC-B-2017 720.2 |
| | CONCEALED INSTALLATION. INSULATING MATERIALS, WHERE |
| | CONCEALED AS INSTALLED IN BUILDINGS OF ANY TYPE OF |
| | CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT |
| | MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE |
| | THAN 450. |
| | |
| | 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| | THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| | DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| | MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| | AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| | |
| | |