| Plan Review Notes For Permit 20040417 |
| Permit Number |
20040417 |
|
| Review Stop |
SIGNATURE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2021-07-12 10:29:26 | SIGNATURE REVIEW COMMENTS. | | | | | | 1-REPEAT COMMENT. PAPER PLANS SUBMITTED DON'T MATCH | | | REVISION UPLOADED TO PROJECTDOX. | | | | | | NOTE: | | | THERE IS A CONFLICT IN THIS SUBMITTAL. THERE ARE TWO | | | DIFFERENT PROJECTS UNDER THIS SUBMITTAL. ONE SET OF | | | PLANS IS FOR FIRE SPRINKLER PLANS FOR THE CLUB@IBIS AND | | | THE OTHER SET OF PLANS IS FOR FIRE SPRINKLER PLANS FOR | | | 205 DATURA ST. | | | UPLOAD THE CORRECT LATEST SET OF PLANS FOR THE CORRECT | | | ADDRESS TO AVOID MORE CONFLICTS. | | | | | | | | | 2- PAPER PLANS SUBMITTED HAVE A COPY OF A DIGITAL | | | SIGNATURE. | | | PLANS NEED TO HAVE THE ENGINEER'S ORIGINAL | | | SEAL/SIGNATURE AS REQUIRED BY 471 F.S. WHEN SUBMITTING | | | PLANS /DOCUMENTS FOR PUBLIC RECORDS. PLANS CAN BE | | | UPLOADED TO PROJECTDOX WITH DIGITAL SIGNATURE OR HARD | | | COPIES WITH ENGINEER'S ORIGINAL SIGNATURE/SEAL MAY BE | | | DROPPED OFF IN CITY HALL. | | | | | | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY | | | QUESTIONS REGARDING THESE COMMENTS, | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|