| Plan Review Notes For Permit 20040372 |
| Permit Number |
20040372 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-04-14 05:34:26 | 1) SHT. P-5 - SHOW THE TYPE OF PIPE AND JOINTS TO BE | | | INSTALLED FOR THE 3-INCH WATER LINE. WPB AMEND. TO FBC | | | SEC. 107.2.1. | | | 2) A REDUCED PRESSURE BACKFLOW PREVENTION DEVICE IS | | | REQUIRED ON THE 3-INCH WATER CONNECTION TO THE CHILLED | | | WATER SYSTEM PER THE CITY OF WEST PALM BEACH | | | CROSS-CONNECTION CONTROL MANUAL. | | | 3) CLEARLY SHOW THE CONNECTION AND LOCATION POINT OF | | | THE 3-INCH DOMESTIC WATER LINE TO THE CHILLED WATER | | | SYSTEM.WPB AMEND. TO FBC SEC. 107.2.1. | | | 4) A SEPARATE PERMIT WILL BE REQUIRED FOR THE BACKFLOW | | | DEVICE THAT IS REQUIRED ON THE 3-INCH DOMESTIC WATER | | | LINE CONNECTION. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | |
|