| 2020-04-14 13:04:54 | REVIEWED BY JERRY SMITH. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| | MANUAL REVISED 2017 |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 20040371 101 N CLEMATIS ST 509 |
| | |
| | 1ST REVIEW |
| | PLUMBING COMMENTS: DENIED |
| | 1. PER WPB FBC 107.2.1, REFERENCING APPLICATIONS ON THE |
| | SUBMITTED SPEC HOME ADVII, INDICATE THE TYPES AND |
| | QUANTITIES OF FIXTURES BEING SERVICED BY THE HA0118240 |
| | UNIT. PROVIDE TOTAL DEMAND FOR UNIT AND INDICATE ON THE |
| | SUBMITTAL WHICH INSERT WILL BE INCORPORATED IN THE |
| | INSTALLATION. |
| | 2. AS THE DOCUMENTS ARE NOT SIGNED AND SEALED BY A |
| | PROFESSIONAL ENGINEER OR ARCHITECT, THE SUBMITTED |
| | DOCUMENTS SHALL BEAR THE PRINTED NAME AND SIGNATURE OF |
| | THE DESIGNER PER WPB FBC 107.2.1. |
| | 3. PER WPB FBC 107.2.1, CONFIRM THAT REPLACEMENT WATER |
| | HEATER IS TO BE INSTALLED IN SAME LOCATION AS THE |
| | REPLACED STORAGE WATER HEATER AND THAT IT IS ACCESSIBLE |
| | IN COMPLIANCE WITH FBC PL 501.4 OR PROVIDE PLAN SHOWING |
| | LOCATIONS IF NOT THE SAME. |
| | 4. UNIT WATTAGE IS 18 KW; TYPICALLY, A STORAGE TYPE |
| | WATER HEATER IS NO MORE THAN 4.5 KW. PER WPB FBC |
| | 107.2.1, AN ELECTRICAL PLAN AND PERMIT APPLICATION |
| | SHALL BE SUBMITTED. |
| | |
| | END OF COMMENTS. |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | ALL PLANS TO BE SIGNED AND SEALED BY THE DESIGNER AS |
| | REQUIRED BY FAC AND FS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL [email protected] |
| | PHONE 561-246-0882 MOBILE |
| | |
| | 20040371 101 N CLEMATIS ST 509 |
| | |
| | |