| 2020-05-14 14:36:33 | 2ND REVIEW FBC-2017 PLUMBING |
| | PERMIT #20040366 |
| | 5/14/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | COMMENT #2 FROM THE 1ST REVIEW PRINTED BELOW WAS NOT |
| | COMPLETELY ADDRESSED. |
| | |
| | 2) PROVIDE A CONDENSATE DISPOSAL DIAGRAM SHOWING HOW |
| | CONDENSATE FROM THE VENT FLUE, AND FROM THE BOILER |
| | NEUTRALIZERS WILL BE DRAINED AND DISPOSED OF- SECTION |
| | 107.2.1 WPB. SEE MECHANICAL COMMENT #1 FOR NEUTRALIZER |
| | PRODUCT SUBMITTAL REQUIREMENT. |
| | |
| | THE REQUESTED DIAGRAM WAS NOT PROVIDED ON SHEET P-001. |
| | AS STATED IN THE NARRATIVE RESPONSE BY THE EOR. SHEETS |
| | P-001 & P-501: |
| | A) PLEASE PROVIDE THE CONDENSATE DRAINAGE DIAGRAM |
| | SHOWING THE DRAIN LINE RUN FROM THE VENT TO THE ACID |
| | NEUTRALIZING TANK, AND THE WASTE LINE RUN FROM THE TANK |
| | TO THE FLOOR DRAIN- SECTION 107.2.1 WPB. |
| | B) P-501: SHOW THE CONDENSATE DRAIN LINE RUN TO THE |
| | ACID TANK, AND THE WASTE LINE RUN TO THE FLOOR DRAIN ON |
| | THE PLAN. |
| | C) 2ND REQUEST TO SUBMIT SPECS FOR THE TANK. PLEASE |
| | NOTE THAT SECTION 803.1 FBC P REQUIRES THAT AN |
| | AUTOMATIC SUFFICIENT SUPPLY OF DILUTING WATER IS |
| | REQUIRED SO AS TO MAKE THE CONTENTS NONINJURIOUS BEFORE |
| | DISCHARGE INTO THE DRAINAGE SYSTEM. THE NATURE OF THE |
| | CORROSIVE OR HARMFUL WASTE AND THE METHOD OF ITS |
| | TREATMENT OR DILUTION SHALL BE APPROVED PRIOR TO |
| | INSTALLATION. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |