| 2020-04-14 13:21:13 | 1ST REVIEW FBC-2017 FUEL GAS |
| | PERMIT #20040366 |
| | 4/142020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | COMMENTS #1 & 2 LISTED BELOW ARE ALSO IN THE MECHANICAL |
| | REVIEW. PLEASE REFER TO MECHANICAL REVIEW COMMENTS FOR |
| | ADDITIONAL PLAN CORRECTIONS. |
| | |
| | 1) PROVIDE A GAS ISOMETRIC DRAWING THAT SHOWS THE TYPE |
| | AND DIAMETERS OF PIPING, THE MEASUREMENTS OF EACH CUT |
| | LENGTH OF PIPE, THE TOTAL DEVELOPED LENGTH OF THE |
| | PIPING RUN FROM THE POINT OF DELIVERY AT THE METER TO |
| | THE MOST REMOTE OUTLET IN THE BUILDING AND TO THE |
| | BOILERS; GAS DELIVERY PRESSURE OF THE SYSTEM AT THE |
| | METER AND AT EACH STEPDOWN REGULATOR; LOCATIONS OF |
| | REQUIRED SHUTOFF VALVES, AND THE BTUH LOADS OF THE NEW |
| | BOILERS, AND ALL OTHER GAS-FIRED APPLIANCES AND |
| | EQUIPMENT BEING SERVED BY THE SYSTEM- SECTIONS 402.2 |
| | AND 402.3 FBC FG. PLEASE INDICATE WHICH PIPE SIZING |
| | TABLES WERE USED IN THE DESIGN- SECTION 402.3. |
| | A) CONCERNING THE REGULATORS PLEASE REFER TO SECTIONS |
| | 410.1, 410.2, & 410.3 FBC FG FOR LINE AND MP REGULATOR |
| | INSTALLATION AND VENTING REQUIREMENTS. PLEASE VERIFY |
| | SUBMITTALS ARE COMPLIANT AND SHOW ALL REGULATOR AND |
| | SHUTOFF VALVES IN THE ISOMETRIC DRAWING, AND REGULATOR |
| | VENT RUNS AND TERMINATION LOCATIONS WHERE REQUIRED. |
| | |
| | 2) PROVIDE A SUBMITTAL PACKAGE THAT INCLUDES |
| | MANUFACTURER'S SPECIFICATIONS AND INSTALLATION |
| | GUIDELINES FOR THE BOILERS, PUMPS, EXPANSION TANK, |
| | CONTROL VALVES, RELIEF VALVES, CHEMICAL FEEDER, |
| | CHEMICAL NEUTRALIZERS, VENT FLUE AND VENT CAP, |
| | COMBUSTION AIR DUCTS, GAS AND HYDRONIC PIPING, AND THE |
| | GAS REGULATORS AND SHUT OFF VALVES- SECTION 107.2.1 |
| | WPB. REVIEW ALL REQUIRED COMPLIANCES AND UL LISTINGS |
| | FOR THE PRODUCTS AS NOTED ON THE SPECIFICATIONS SHEETS |
| | M101, 102, & 103 AS THEY WILL BE CROSS CHECKED IN THE |
| | 2ND REVIEW. THE DESIGN PROFESSIONAL OF RECORD SHALL |
| | PROVIDE APPROVAL STAMPS ON EACH SUBMITTAL DOC, OR |
| | PROVIDE A STAMPED COVER PAGE WITH AN INDEX LISTING ALL |
| | PRODUCT SUBMITTALS. |
| | |
| | A) PLEASE NOTE THE GAS BOILER SPECIFICATIONS SHALL |
| | INDICATE THAT THE UNITS ARE LISTED IN ACCORDANCE WITH |
| | THE REQUIREMENTS OF ANSI Z21.13 OR UL 795, AND DESIGNED |
| | AND CONSTRUCTED IN ACCORDANCE WITH THE REQUIREMENTS OF |
| | ASME CSD-1 AND AS APPLICABLE, THE ASME BOILER AND |
| | PRESSURE VESSEL CODE, SECTIONS I, II, IV, V AND IX AND |
| | NFPA 85- SECTION 631.1 FBC FG AND SECTION 1004.1 FBC M |
| | |
| | 3) REFER TO SECTIONS 406.4, THROUGH 406.6 FBC FG AND |
| | PROVIDE A GAS PIPING TESTING PROCEDURE ON THE PLAN. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |