| Plan Review Notes For Permit 20040366 |
| Permit Number |
20040366 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-04-15 16:24:47 | REPLACING AND ADDING BOILERS | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected]. | | | | | | CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 | | | | | | 1) PLEASE SHOW THE EXISTING HOURLY FIRE RATING FOR THE | | | WALLS. | | | 2) PLEASE SHOW IF THE BUILDING HAS EXISTING FIRE | | | SPRINKLERS. | | | 3) PLEASE SHOW PENETRATIONS THRU FIRE RATED WALLS TO | | | COMPLY WITH FBC 714 | | | FBC EXISTING BUILDING 703.1GENERAL. | | | ALTERATIONS SHALL BE DONE IN A MANNER THAT MAINTAINS | | | THE LEVEL OF FIRE PROTECTION PROVIDED. | | | PLANS DO NOT SHOW ANY NEW WALLS. |
|