| 2020-04-16 09:09:43 | 1ST REVIEW FBC-2017 PLUMBING |
| | PERMIT #20040270 |
| | 4/15/20 |
| | |
| | CODES IN EFFECT. |
| | |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET ALS1 CODE DATA: PLEASE PROVIDE A SCHEDULE |
| | INDICATING THE REQUIRED AND THE PROVIDED NUMBER OF |
| | PLUMBING FIXTURES FOR THE NEW TENANT OCCUPANCY- REFER |
| | TO TABLE 403.1 FBC P. ACCORDING TO THE TABLE A DRINKING |
| | FOUNTAIN AND A SERVICE SINK ARE REQUIRED FOR BUSINESS |
| | OCCUPANCIES, AND THE DRINKING FOUNTAIN IS REQUIRED TO |
| | BE ACCESSIBLE PER SECTION 211.1 FBC ACC. PLEASE NOTE |
| | THAT THE CUSTOMER SUPPLIED WATER COOLER CAN NOT |
| | SUBSTITUTE FOR THE REQUIRED ACCESSIBLE FOUNTAIN- |
| | SECTION 211.1 FBC ACC. |
| | |
| | 2) A1.1.1 & A3.01: THE DRAWINGS INDICATE ONE ACCESSIBLE |
| | UNISEX TOILET ROOM AND ONE NON-ACCESSIBLE. IN |
| | ACCORDANCE WITH SECTION 213.2 FBC ACC BOTH TOILET ROOMS |
| | SHALL BE ACCESSIBLE, UNLESS MEETING ONE OF THE |
| | EXCEPTIONS LISTED UNDER THIS SECTION, OR SEEKING AN |
| | ALTERNATE APPROVAL BASED ON DISPROPORTIONATE COST- |
| | 202.4.1 FBC ACC. |
| | |
| | 3) A3.01, ACCESSIBLE UNISEX TOILET ROOM: A) SHOW THE |
| | CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| | ACCESSIBLE LAVATORY- SECTION 606.2 FBC ACC. B) SHOW THE |
| | 60? DIAMETER CIRCULAR TURNING SPACE- SECTION 304.3.1. |
| | C) IT APPEARS THE DOOR WILL SWING INTO THE CLEAR FLOOR |
| | SPACE AT THE LAVATORY- SECTION 603.2.3, SEE EXCEPTION |
| | 2. |
| | |
| | 4) A3.01, DETAIL 7: SHOW THE REQUIRED KNEE AND TOE |
| | CLEARANCES AT THE ACCESSIBLE LAVATORY- SECTIONS 306.2 & |
| | 306.3 FBC ACC. |
| | |
| | 5) A3.01, DETAIL 5: THE SIDE GRAB BAR SHALL EXTEND A |
| | MINIMUM 54" OUT FROM THE REAR WALL- SECTION AND FIGURE |
| | 604.5.1 FBC ACC. |
| | |
| | 6) A1.1.1 & A304: SHOW THE CLEAR FLOOR SPACE DIAGRAMS |
| | AND DIMENSIONS AT THE KITCHEN SINK, THE DISHWASHER, THE |
| | COFFEE MACHINE, AND THE WATER COOLER- SECTIONS 606.2 |
| | AND 804.6 FBC ACC. PLEASE NOTE THE CLEAR FLOOR OR |
| | GROUND SPACE FOR THE DISHWASHER SHALL BE POSITIONED |
| | ADJACENT TO THE DISHWASHER DOOR. THE DISHWASHER DOOR, |
| | IN THE OPEN POSITION, SHALL NOT OBSTRUCT THE CLEAR |
| | FLOOR OR GROUND SPACE FOR THE DISHWASHER OR THE SINK- |
| | SECTION 804.6.3 FBC ACC. |
| | |
| | 7) A1.1.1 & A3.04: SHOW COMPLIANCE WITH REQUIRED REACH |
| | RANGES AND OPERABLE PARTS FOR THE DISHWASHER, THE |
| | COFFEE MACHINE, AND THE WATER COOLER- SECTIONS 804.6.2, |
| | 308, & 309 FBC ACC. |
| | |
| | 8) A3.01: PLEASE CLARIFY WHY MEN'S AND WOMEN'S MIRRORS |
| | ARE DESIGNATED IN THE TOILET ACCESSORIES SCHEDULE FOR |
| | UNISEX BATHROOMS- SECTION 107.22.1 WPB. |
| | |
| | 9) A3.04, DETAIL 4: THE KITCHEN COUNTER WORK SURFACE |
| | HEIGHT SHALL BE 34" MAXIMUM ABOVE THE FINISHED FLOOR- |
| | SECTION 804.3.2 FBC ACC. |
| | |
| | 10) P0.1: SHOW THE LOCATIONS OF THE HOT WATER FIXTURE |
| | SUPPLY SHUT OFF VALVES AT THE PUBLIC LAVATORY SINK |
| | DETAILS- SECTION 606.2(1) FBC P. |
| | |
| | 11) P0.1, WATER RISER: SHOW THE WATER SUPPLY CONNECTION |
| | TO THE COFFEE MAKER WITH THE REQUIRED BACKFLOW |
| | PREVENTER- SECTION 608.1.6.10 FBC P. |
| | |
| | 12) P0.1 PROVIDE A BACKFLOW SCHEDULE INDICATING WHICH |
| | TYPES WILL BE INSTALLED AT THE WATER DISPENSER, ICE |
| | MAKER, AND DISHWASHER- SECTION 608.13 FBC P. |
| | |
| | 13) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| | TANKLESS WATER HEATERS- SECTION 107.2.1 WPB |
| | |
| | 14) PROVIDE A SLAB REPAIR DETAIL- SECTION 107.2.1 WPB |
| | FBC |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | CHRISTOPHER L. COLE |
| | PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |