| Plan Review Notes For Permit 20040247 |
| Permit Number |
20040247 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-04-14 15:01:15 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE FLOOR PLAN IS REQUIRED TO HAVE THE PRINTED NAME | | | AND SIGNATURE OF THE PERSON RESPONSIBLE FROM THE | | | DRAWING. FBC 107.2.1 - INFORMATION ON CONSTRUCTION | | | DOCUMENTS. ALL INFORMATION, DRAWINGS, SPECIFICATIONS | | | AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | | | 2) THE FLOOR PLAN SHOWS A MULLION AND A SLIDING GLASS | | | DOOR IN OPENING NUMBER 6. PLEASE CLARIFY WHAT THE | | | MULLION IS BEING USED FOR. PROVIDE A DETAIL FOR THIS | | | OPENING. FBC 107.2.1.2 |
|