| Plan Review Notes For Permit 20040240 |
| Permit Number |
20040240 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2020-05-04 15:47:01 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2017 6TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | | NFPA 70 2014 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) FAULT CURRENT CALCULATIONS REQUIRED 110.9, 110.10 | | | | | | PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH | | | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY | | | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR | | | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE | | | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. | | | NEC 110.9, 110.10 | | | | | | 2) 210.64 ELECTRICAL SERVICE AREAS AT LEAST ONE | | | 125-VOLT, SINGLE-PHASE, 15- OR 20-AMPERE-RATED | | | RECEPTACLE OUTLET SHALL BE INSTALLED WITH IN 15 M (50 | | | FT) OF THE ELECTRICAL SERVICE EQUIPMENT. | | | |
|