Plan Review Notes
Plan Review Notes For Permit 20040233
Permit Number 20040233
Review Stop E
Sequence Number 2
Notes
Date Text
2020-06-03 12:57:18CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS
 COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY
 HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW
 COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS.
  
 1. PLAN STATES THERE IS NO CHANGE TO THE RISER DIAGRAM,
 BUT THE LOAD TABLE STATES THE UPGRADED ELECTRICAL
 SERVICE IS 200 AMPS. WHICH IS IT? PROVIDE
 CLARIFICATION. PROVIDE RISER DIAGRAM OF EXISTING
 SERVICE. NEC 215.5; WPB FBC 107.2.1 (THERE ARE
 DISCREPANCIES WITH THE RISER DIAGRAM. IS THIS A 200 AMP
 AS INDICATED IN THE MAIN PANEL SCHEDULE? OR IS THIS A
 400 AMP PANEL AS INDICATED IN THE RISER DIAGRAM? OR IS
 THIS A 325 AMP SERVICE AS INDICATED IN THE RISER
 DIAGRAM? INFORMATION ON PLAN NEEDS TO BE CONSISTENT.
 WIRE SIZE IS DETERMINED BY THE OVER CURRENT PROTECTION
 OF THE MAIN PANEL. PROVIDE CORRECTION AND
 CLARIFICATIONS.)
 2. CORRECTED.
 3. CORRECTED.
 4. CORRECTED.
 5. IF NEW SERVICE IS TO BE INSTALLED, PROVIDE AVAILABLE
 SHORT CIRCUIT CALCULATION FOR SERVICE INCLUDING
 INFORMATION FROM THE POWER COMPANY STATING WHAT THE
 AVAILABLE SHORT CIRCUIT CURRENT IS FOR THE SERVICE TO
 CONFIRM THE STATED AIC RATING OF THE SERVICE EQUIPMENT
 IS ADEQUATE. NEC 110.9, 110.10; FBC RE E3606.3 (NOT
 PROVIDED.)
 6. CORRECTED.
 7. CORRECTED.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH
 ITEM ALONG WITH THE CITY RESUBMITTAL FORM.
 ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED OLD SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  