2020-04-20 13:44:051) PLANS ARE REQUIRED TO BE DIGITALLY SIGNED AND SEALED
 PER FL. ADMIN. CODE RULE 61G15-23.004, 61G15-23.005.
 2) THE GAS POOL HEATERS SHALL HAVE A MINIMUM 82%
 EFFICIENCY PER 2017 FBC-ENERGY TABLE C404.2.
 3) OUTDOOR HEATED SWIMMING POOLS SHALL BE EQUIPPED WITH
 A VAPOR-RETARDANT COVER ON OR AT THE WATER SURFACE OR A
 LIQUID COVER OR OTHER MEANS PROVEN TO REDUCE HEAT LOSS
 PER 2017 FBC-ENERGY SEC.C404.9.3.
 4) THE PLANS NOTE THE OVERFLOW LINE FOR THE POOL SHALL
 DISCHARGE TO THE STORM SYSTEM AND THE POOL WASTE TO
 DISCHARGE TO THE SANITARY. POOL WATER CANNOT DISCHARGE
 TO THE STORM SYSTEM OR TO THE SANITARY SYSTEM PER CITY
 OF WEST PALM BEACH CODE OF ORDINANCES CHAPTER 90,
 ARTICLE V, SEC. 90-203 (A) & CHAPTER 90, ARTICLE III,
 SEC. 90-126 (5). PERMISSION MUST BE OBTAINED FROM THE
 CITY OF WPB ENGINEERING DEPT.PLEASE CONTACT MANNY
 GONZALEZ IN THE ENGINEERING DEPT. AT 561-494-1085 -FOR
 FURTHER DIRECTION. THIS INFORMATION/DETAIL APPEARS ON
 SEVERAL SHEETS OF THE PLANS AND ALL SHEETS SHALL BE
 REVISED TO COMPLY WITH THE DECISION FROM THE CITY'S
 ENGINEERING DEPARTMENT. REFER TO SHEETS SP-1.06 ( POOL
 PIPING LEGEND NOTES G, I, K ) ET.AL.
 5) SHT. SP-1.07 - DETAIL #11 REFERS TO POOLS WITH FLOOR
 INLETS ONLY. THIS POOL HAS WALL INLETS IN ADDITION TO A
 COUPLE FLOOR INLETS. CLARIFY.
 6) SHT.SP-1.08 - DETAIL #3 - ITEM D1 ON THE POOL PIPING
 ISOMETRIC IS NOT LISTED IN THE LEGENDS ON SP-1.06, OR
 SP-1.10. CLARIFY.
 7) SHT. SP-1.09 SHOWS THE COLLECTOR TANK AS 300 GALLONS
 BUT THE FILTRATION EQUIPMENT TABLE ITEM #27 ON SHT.
 SP-1.10 CALLS OUT THE COLLECTOR TANK AS 525 GALLONS.
 CLARIFY.
 8) A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW
 PREVENTION DEVICE ON THE WATER FILL LINE. THE DEVICE
 MUST BE LEAD FREE PER THE CITY OF WPB CROSS CONNECTION
 CONTROL MANUAL.
 9) A SEPARATE GAS PERMIT IS REQUIRED FOR THE
 INSTALLATION OF THE GAS POOL HEATERS.
 10) THE PLANS REFER TO THE CIVIL DRAWINGS FOR THE
 CONTINUATION OF THE OVERFLOW AND POOL WASTE LINES.THERE
 ARE NO CIVIL DRAWINGS WITH THESE PLANS. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  