| 2020-06-05 12:04:45 | 3RD REVIEW FBC RES 2017 |
| | PERMIT 20040217 |
| | 6/5/2020 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH |
| | EDITION 2017 |
| | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | COMMENTS FROM THE 2ND REVIEW BELOW WILL BE MARKED AS |
| | PASSED OR FAILED. SEE NOTES ADDED FOR FAILED COMMENTS. |
| | |
| | 1) PASSED. |
| | 2) PASSED. |
| | |
| | 3.) PASSED. LIST THE BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2017 |
| | FBC-FUEL GAS SECS.401.8, 402.2, AND TABLES 402.4 (1) |
| | THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2413.4 |
| | AND TABLES G2413.4 (1 ) THROUGH G2413.4 (21). |
| | |
| | 4.) PASSED SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (GAS METER / MP REGULATOR / LP TANK) TO THE |
| | MOST REMOTE OUTLET IN THE BUILDING AND / OR SYSTEM PER |
| | THE 2017 FBC-FUEL GAS SEC.402.4.1, 402.4.2, OR 2017 |
| | FBC-RES. SEC. G 2413.4.1, G2413.4.2. |
| | |
| | 5.) FAILED SUBMIT CALCULATIONS FOR COMBUSTION AIR. |
| | PROVIDE VERIFICATION & CALCULATIONS AS TO HOW THE |
| | REQUIREMENTS ARE BEING MET. PROVIDE THE CODE SECTIONS |
| | FROM THE GAS CODE THAT YOU ARE USING IN THE DESIGN OF |
| | THE COMBUSTION AIR REQUIREMENTS PER THE 2017 FBC-FUEL |
| | GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR 2017 |
| | FBC-RES. SEC.G 2407.1 AND G2439.4 (CLOTHES DRYERS). |
| | SECTION G2407.1- MAKEUP AIR NOT PROVIDED FOR THE |
| | CLOTHES DRYER. DETAIL 4/P1 INDICATES OUTDOOR AIR WHICH |
| | WOULD REQUIRE AN OPENING OR OPENINGS TO THE EXTERIOR |
| | PER SECTIONS G2407.6- G2407.7. FBC RES. |
| | |
| | 6) PASSED |
| | |
| | 7) FAILED. SUBMIT TWO COPIES OF A DETAIL SHOWING THE |
| | TYPE OF VENT, LOCATION, SIZE, TERMINATION POINT, HEIGHT |
| | ABOVE THE ROOF AND ANCHORING DETAILS OF THE GAS VENT(S) |
| | PER 2017 FBC-FUEL GAS SECS. 502 THRU 505 OR 2017 |
| | FBC-RES. SEC.G2426 THROUGH G2439. THE REVISED DETAIL ON |
| | P1 DOES NOT SHOW THE METAL FLUE VENT SIZE, TOTAL VENT |
| | LENGTH AND TERMINATION POINT WITH PROPER TERMINATION |
| | CAP. PLEASE PROVIDE THE CORRECT RINNAI MODEL NUMBER ON |
| | THE PLAN AND REVIEW THE VENTING SPECIFICATIONS ON PAGE |
| | 7-8 OF THE MANUFACTURER?S SPECIFICATIONS. THE VENT FLUE |
| | IS NOT REQUIRED [PER THE SPECS BUT PROPER CLEARANCES |
| | ARE. PLEASE SHOW COMPLIANCE. |
| | |
| | 8) PASSED. SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| | SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| | NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND |
| | 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES |
| | SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS |
| | FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT |
| | THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. |
| | SEC.G2408.1. |
| | |
| | 9) FAILED. SUBMIT TWO COPIES OF THE APPLICABLE SIZING |
| | TABLES USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON |
| | THE PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) |
| | FROM THE GAS CODE OR OTHER STANDARD THAT WERE USED IN |
| | THE DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 |
| | FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND TABLES |
| | 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC. |
| | G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3. TABLE |
| | 402.4(9) CALLED OUT ON THE ISO IS FOR SEMI-RIGID COPPER |
| | TUBING, BUT SCHEDULE 40 METALLIC PIPE IS CALLED OUT FOR |
| | INSTALLATION. PLEASE NOTE THAT DETAIL 1/P-2 DOES NOT |
| | SHOW THE GAS LINE RUNS TO THE WATER HEATER, STOVE, AND |
| | THE DRYER. PLEASE NOTE THAT THE GAS PIPING INSTALLATION |
| | MAY BE DONE UNDER A SEPARATE PERMIT IF THAT WOULD |
| | FACILITATE THE ISSUANCE OF THE MAIN PERMIT. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL/PLUMBING PLANS EXAMINER |
| | 401 CLEMATIS STREET |
| | WEST PALM BEACH FL 33401 |
| | 561-805-6719 |
| | [email protected] |
| | |
| | |